Polywater ZipSeal vs FST vs AFT: Which Conduit and Duct Sealant to Use

June 15, 2020

Polywater ZipSeal vs FST vs AFT: Which Conduit and Duct Sealant to Use

Polywater makes three foam sealants for conduit and duct. FST is a caulking-tube foam for conduits from 2 to 8 inches. AFT is an aerosol foam for conduits from 3/4 to 10 inches. ZipSeal is a two-syringe foam kit for small conduits, communication innerducts and thin annular spaces. All three are two-part urethane foams that expand and harden into a closed-cell seal that blocks water and gas.

ZipSeal, FST and AFT Side by Side

ZipSealFSTAFT
FormTwo 25 ml syringes with mixing nozzlesCaulking tube with mixing nozzle16 oz aerosol can
Best forSmall conduits, communication innerducts, thin annular spacesConduits from 2 to 8 inchesConduits from 3/4 to 10 inches
Water head30 ft (9 m)22 ft continuous, 90 ft intermittent11 ft on PVC, 6 ft on rigid steel
GasBlocks gas and waterBlocks at least 5 psi; passed 20 psi for 168 hoursHeld 2 psi for 48 hours on PVC
Application temperature35 to 95 degrees F35 to 95 degrees F45 to 95 degrees F
Service temperature-20 to 200 degrees F continuous, -40 to 250 degrees F peak-20 to 200 degrees F continuous-20 to 200 degrees F
SetupMesh strip for horizontal and vertical runsDamming strips hold the foam; works in any orientationFoams immediately; works vertically without a dam
Foaming at 70 degrees FFully expanded in about 1 minute, hard in 24 to 5 minutes, skin in 7 to 9Rises in 2 to 3 minutes, tack-free in 3 to 5
Contact length along the cableAbout 2 in. (5 cm)About 3 in. (7.6 cm)About 6 in. (15 cm)
Seals per packageOne cartridge seals from five 2 in. ducts up to fifteen 1 in. ductsDepends on conduit size and fill; Polywater has an FST foam quantity calculatorOne can seals from one 8 in. conduit up to fifteen 2 in. conduits
FireFlame retardantFire retardant under UL 94; classified for surface burning characteristicsUL Recognized to UL 94, Class HBF
Shelf lifeA part-used syringe keeps for up to a month in its pouch15 months; one month once opened12 months

Polywater's FAQ says to position cables before sealing, because wires can't be moved after injection. The foams are removable: pierce the foam around the inner wall with a long rigid tool, break the bond, and pull the plug.

Which One for Which Job

JobPickWhy
Communication innerducts and small conduitsZipSealSyringe kit sized for small ducts and thin annular spaces
Large conduits entering a vault, building or manholeFSTTested to 8 in. and rated 22 ft continuous
Vertical conduits or quick jobs on many sizesAFTAerosol foam rises right away, with no dam needed vertically
Mixed conduit sizes on one jobAFTOne can seals from one 8 in. conduit to fifteen 2 in. conduits

Catalog Numbers

ProductCatalog numberWhat it is
FSTFST-250Caulking tube, 1 mixing nozzle, resealing cap
FSTFST-250KIT1Tube, 3 nozzles, 4 damming strips, abrasive strip, gloves, positioning rod, wipe, cap, instructions
FSTFST-250KITCase of 6 FST-250KIT1 kits
FSTTOOL-250High-ratio dispensing tool, sold separately
FSTMXR-41T-10, FST-DAM10-pack of mixing nozzles; one 24 in. damming strip
AFTAFT-16One 16 oz can with 2 actuators
AFTAFT-16P4Four-can version
AFTAFT-SAE10, AFT-FAE1010-pack of actuators with standard or flexible extension tube
ZipSealZIP-25KIT12 x 25 ml syringes, 5 mixing nozzles, mesh strip, gloves, instructions
ZipSealZIP-25KITB6, MXR-24L-10Case of 6 kits; 10-pack of nozzles

ZipSeal: How Much Foam per Duct

Polywater's instruction sheet (87037-002) gives approximate quantities. A mark is a graduation on the side of the syringe.

Duct sizeLiquid ZipSealMesh strip needed
3/4 in. (20 mm) and below1 full mark1 in. (25 mm) or less
1 in. (25 mm)2 full marks1 in. (25 mm)
1 1/4 in. (32 mm)2 full marks2 in. (50 mm)
1 1/2 in. (38 mm)3 full marks4 in. (100 mm)
2 in. (50 mm)5 full marks6 in. (150 mm)

Installing ZipSeal

StepWhat to do
1Clear loose debris or rust and clean the surfaces. Let any solvent dry first. Sand or abrade for best adhesion. Steel conduit must be sanded and cleaned.
2Tear off the mesh strip length from the table and insert it 1 in. past the duct opening. Weave it between the wires to separate them.
3Screw the static mixer onto the upright syringe
4Inject a full mark at each injection point, about 5 seconds per mark, from the bottom of the opening to the top and around the wires and edges. The more you spread the injections, the better.
5Do not count marks until foam leaves the mixer tip. Insert the mixer about 1 in. into the mesh strip.
6Foam starts to expand in 10 to 20 seconds. Do not move the wires. Then take off the mixer and put the plug back on right away.
7It is fully expanded in about 1 minute and hard in 2. Look for gaps and fill them with more foam.

For vertical work, wrap the mesh tighter and insert it about 3 in. deep. For annular spaces, Polywater gives about 1.25 cubic inches (20 cm3) per mark. For an active water leak, Polywater describes a double-seal method: a first seal to stop most of the flow, then dry the duct and make the full seal. Install between 35 and 95 degrees F. Wear eye protection and gloves.

Sealing a Vertical Conduit

All three sealants work in vertical conduits. FST and ZipSeal are liquid when dispensed, so something has to hold them in place while they expand and cure. AFT foams immediately. This is how Polywater's FAQ describes each one.

SealantHow it goes in
FSTInsert both damming strips to make a 3 in. (7.6 cm) cavity, then inject through the gap between the strips at the conduit mouth. Polywater recommends using both strips so the foam builds pressure and contacts the surfaces for a solid seal.
ZipSealThe FAQ describes sizing the saturated Zip-Disc to the duct, inserting it, and injecting into the center black mesh. Space full injections about 1/2 in. (1.3 cm) apart, each in a different spot. The instruction sheet above describes a mesh strip for the same job.
AFTPlace damming about 6 in. (15 cm) into the conduit, invert the can, insert the nozzle deep and spray for the recommended time. Hold a gloved hand or a piece of cardboard over the duct mouth for about 2 to 3 minutes at room temperature.

Cables, Cure Time, Nozzles and Removal

These points come from the same Polywater FAQ and apply to all three foams unless noted.

TopicWhat Polywater says
Separating cablesSeparating the cables gives a better seal. The damming strips in FST kits keep cables off the conduit wall so the foam can bond all the way around.
Moving cablesNever move the cables after injecting. Position them before you seal.
Cold weatherFoam does not cure below 40 degrees F (4 degrees C).
Cure timesAt 40 degrees F, expansion finishes in 8 to 9 minutes and a non-sticky skin forms in 15 to 18 minutes. At 70 degrees F (21 degrees C), expansion takes 4 to 5 minutes and the skin forms in 7 to 9 minutes.
Reusing a nozzleA nozzle can be used for back-to-back seals if it sits no longer than 1 to 2 minutes between injections. After that it is single use, because the two-part foam cures inside it.
RemovalPierce the foam around the inner wall of the conduit with a long-handled screwdriver to loosen the bond, then pull the plug out and free it from the cable. Duct putty is easier to remove but does not seal as well.
Crushing cables or bursting conduitThe foams do not have the expansion force to crush cables or burst conduit. Extra foam escapes through the path of least resistance, which is the damming at the conduit mouth.
Wall penetrationsFoam can seal around the outside of a conduit passing through a wall where fire blocking is not required. The void must be enclosed with damming, which can come out after curing. Fill large voids in stages.
Cable jacketsAll three are compatible with common jacket materials. Cured foam is inert, and tensile elongation and volume resistivity testing showed no change to the cable.
RodentsThe hermetic seal keeps rodents from smelling food through the conduit, which makes it an effective deterrent.
HeatA seal insulates the cable where it sits, but it is a small part of the run.
FST in serviceMade for long-term use. It yellows in sunlight without affecting performance and can be painted for UV protection. It resists dilute acids and bases, gasoline, oils and most unsaturated hydrocarbons.

Listings, Fire Ratings and Code Requirements

Polywater's FAQ answers the questions inspectors and engineers ask most.

QuestionWhat Polywater says
UL or CSA approvalUL and CSA have no specific tests for conduit sealants. Polywater formulates its sealants to block water and gas and to resist rodents.
What the codes ask forNorth American electrical codes call for sealing that is compatible with the wire and jacket materials, keeps out moisture and gas, is installed where temperature changes occur, and is installed underground at one or both ends of the conduit. Polywater says other regions often have similar rules.
Authority having jurisdictionApplied per the instructions, the sealants generally meet these requirements. Some authorities may ask for third-party testing or manufacturer documentation.
UL Listed or UL RecognizedUL Listed covers complete standalone products. UL Recognized covers components. AFT is UL Recognized.
FireFST is fire retardant under UL 94 and classified for surface burning characteristics in the US and Canada, and is ULC Classified. AFT is UL Recognized to UL 94, Class HBF. ZipSeal is flame retardant.
Class 1 Div 1Not permitted with foam sealant alone. Sealants and fittings are approved only in tested combinations, so the exact tested pairing has to be used.
SafetyFST, AFT and ZipSeal are considered safe when used as the manufacturer recommends. Sensitivity to chemicals varies from person to person.
CostTwo-part foam sealants usually cost less per seal than most alternatives, because one cartridge or can makes several seals.

FAQ

Which sealant works on a vertical conduit?

All three. AFT foams immediately, so it is the quickest. FST needs both damming strips and ZipSeal needs its mesh or disc to hold the liquid until it expands.

Can I get back into the conduit later?

Yes. Break the foam bond around the inner wall with a long rigid tool and pull the plug.

Will it cure in cold weather?

The data sheets list application from 35 degrees F for ZipSeal and FST and from 45 degrees F for AFT. Polywater's FAQ says foam does not cure below 40 degrees F (4 degrees C), and that at 40 degrees F expansion takes 8 to 9 minutes against 4 to 5 at 70 degrees F.

Is cured foam fire rated?

FST is fire retardant under UL 94 and classified for surface burning characteristics. AFT is UL Recognized to UL 94 Class HBF. ZipSeal is flame retardant. Foam alone is not approved for Class 1 Div 1 locations.

Is there a UL or CSA listing for conduit sealants?

Polywater says UL and CSA have no specific tests for them. AFT is UL Recognized as a component, and FST is ULC Classified.

Can foam crush cables or burst a conduit?

No. Polywater says the foams lack the expansion force, and extra foam escapes at the damming.

Can I reuse the mixing nozzle?

Only for back-to-back seals. If it sits more than 1 to 2 minutes the foam cures inside it and it is single use.

Does foam keep rodents out?

Yes. Polywater says the hermetic seal keeps rodents from smelling food through the conduit.

Will the foam hurt the cable jacket?

No. Polywater says all three are compatible with common jacket materials, and testing showed no change in tensile elongation or volume resistivity.

Where to Buy

Contact Powertech Associates at info@powertech-upsc.com or (860) 678-8772 with the conduit size and location.

Learn more from Polywater: ZipSeal product page, ZipSeal flyer, FST data sheet, AFT data sheet and the foam sealing FAQ.

Last updated: November 2026.

Interested in this product?

Contact us, request a quote, or order online.