.webp)
Raychem HVSY heat shrink wye tap splices make a branch connection on 1/C poly-poly, PILC-PILC and PILC-poly cable up to 15 kV. They seal against water with a branch clip and TE's heavy-duty MBSM wraparound sleeve, and TE lists them as qualified to IEEE 404. The HVSY-1520S kits are for polymeric cable, and the HVSY-1580D kits are for wye splices where the main or tap cable may be paper insulated lead covered (PILC) or varnished cambric lead covered (VCLC).
Pick by the main and tap conductor size and insulation diameter. The kits do not include connectors.
| Catalog number | TE part # | Conductor, AWG/kcmil | Insulation diameter, mm (in) | Pack |
|---|---|---|---|---|
| HVSY-1522S | 722789-000 | 2 to 4/0 main and tap | 17 to 27 (0.65 to 1.05) | 1 kit per box |
| HVSY-1523S | 770433-000 | 250 to 750 main, 2 to 750 tap | 24 to 37 main, 17 to 37 tap (0.95 to 1.45 main, 0.65 to 1.45 tap) | 1 kit per box |
| Item | TE says |
|---|---|
| Voltage class | Up to 15 kV |
| Cable | 1/C poly-poly, PILC-PILC and PILC-poly |
| Technology | Heat shrink tap splice with a clip closing |
| Shield | Copper tape, wire shield, lead sheath and UniShield cables |
| Sealing | Internal moisture seals for a redundant seal against water, plus a branch clip and the MBSM wraparound sleeve |
| Shape | Compact, which simplifies cable training |
| Standard | IEEE 404 |
| Where installed | Direct buried, manholes and cable trays |
All HVSY kits install to 30 in (750 mm) and need 45 in (1125 mm) of installation space, according to TE. The connector length limit depends on the kit.
| Kit | Max connector length, in (mm) | Installed length, in (mm) | Installation space, in (mm) |
|---|---|---|---|
| HVSY-1522S | 3.0 (75) | 30 (750) | 45 (1125) |
| HVSY-1523S | 3.5 (90) | 30 (750) | 45 (1125) |
The kits do not contain connectors. The first two rows are for soldered connectors. The rest are for Burndy YSH crimp connectors, which TE lists for copper conductors only. Insulation diameters are in mm (in).
| Kit | Connector | Main conductor | Tap conductor | Main insulation | Tap insulation |
|---|---|---|---|---|---|
| HVSY-1522S | Soldered | 2 to 4/0 | 2 to 4/0 | 17 to 27 (0.65 to 1.05) | 17 to 27 (0.65 to 1.05) |
| HVSY-1523S | Soldered | 250 to 750 | 2 to 750 | 24 to 37 (0.95 to 1.45) | 17 to 37 (0.65 to 1.45) |
| HVSY-1522S | Burndy YSH-2929 | 2 to 4/0 | 2 to 4/0 | 17 to 27 (0.65 to 1.05) | 17 to 27 (0.65 to 1.05) |
| HVSY-1523S | Burndy YSH-3434 | 250 to 500 | 4/0 to 500 | 22 to 32 (0.85 to 1.25) | 22 to 32 (0.85 to 1.25) |
| HVSY-1523S | Burndy YSH-3939 | 500 to 750 | 350 to 750 | 28 to 37 (1.10 to 1.45) | 25 to 37 (1.00 to 1.45) |
For HVSY-1520S kits on copper conductors only, TE says Burndy H-tap compressed connectors may be used in place of the half-duplex connector. For a 15 kV H configuration on 1/C shielded power cable, TE says to order the HVSH-1520 mod kit along with the right HVSY-1520S kit.
The HVSY-1580D is TE's 15 kV wye splice for PILC and PILC-poly cable. It is for splices where the main or tap cable may be paper insulated lead covered cable or varnished cambric insulated lead covered cable.
| Kit | Conductor, AWG/kcmil | Insulation diameter, mm (in) | Max connector length, in (mm) | Installed length, in (mm) | Installation space, in (mm) |
|---|---|---|---|---|---|
| HVSY-1582D | 2 to 4/0 main and tap | 17 to 27 (0.65 to 1.05) | 3.0 (75) | 30 (750) | 45 (1125) |
| HVSY-1583D | 250 to 750 main, 2 to 750 tap | 24 to 37 main, 17 to 37 tap (0.95 to 1.45 main, 0.65 to 1.45 tap) | 3.5 (90) | 30 (750) | 45 (1125) |
These notes are from TE's ordering information.
| Note | TE says |
|---|---|
| Selection basis | Selections are based on typical dimensions of 100% and 133% insulated cable and commonly used connectors made to AEIC standards |
| Nominal insulation thickness | 100%: 165 mils for PILC/VCLC and 175 mils for poly. 133%: 220 mils for poly |
| Other cable specs | Confirm the selection with the cable and connector dimensions |
| Fit | Check the poly cable insulation diameter to help ensure a proper fit |
| Connectors | Kits do not contain connectors. Contact TE for connector information |
| Package | 1 kit per box |
| Kit family | TE test reports |
|---|---|
| HVSY-1520S | EDR-5236 and EDR-5256 |
| HVSY-1580D | EDR-5235 |
A splice that makes a branch connection from a main cable to a tap cable.
Up to 15 kV.
No. Order solder or Burndy YSH crimp connectors separately.
The HVSY-1522S covers 2 to 4/0 main and tap.
The HVSY-1523S covers 250 to 750 main and 2 to 750 tap.
Yes. TE lists the HVSY series for PILC-PILC and PILC-poly cable. For a wye splice where the main or tap may be PILC or VCLC cable, use the HVSY-1580D series.
For 15 kV H-configuration connections on 1/C shielded power cable, TE says to order the HVSH-1520 mod kit with the right HVSY-1520S kit.
TE says the HVSY is not part of its standard installation training because the application is specific. TE offers specialized support through TE.com/trainingcenter.
Utility Power Supply Company (UPSC) and Powertech Associates supply TE Raychem products across New England and New York State. The HVSY-1522S and HVSY-1523S are in our online store. For the HVSY-1582D and HVSY-1583D PILC kits, connectors, the HVSH-1520 mod kit or anything else, contact Powertech Associates at info@powertech-upsc.com or (860) 678-8772.
For other heat shrink products, see the TE Raychem heat shrink tubing selection guide.
Last updated: November 2026.