A pin terminal lands a cable on a bolted or plug-in connection. Richards makes the APT for aluminum and ACSR cable, and the CPT for copper cable. If you are tying several cables together instead, see the Richards crab joints guide.
Start with what the cable is made of.
| Family | What it is for | Material and notes |
|---|---|---|
| APT | Aluminum and ACSR cable, also accepts copper | High-conductivity aluminum barrel with a tin-plated copper pin, oxide-inhibiting compound inside, marked with conductor size and die |
| CPT | Copper cable | Seamless copper barrel, solid copper pin, brazed for a watertight joint, hot tin dipped, crimped with standard dies |
Pins come in any length, and the standard pin length is 6 in. Dimensions L, D and OD are in inches as Richards lists them. For other sizes, contact us.
| Part | Aluminum cable | Installing dies | Pin dia. (in) | L | D | OD |
|---|---|---|---|---|---|---|
| APT3 | #6 | TWTY, 297, 5/8-1 | 0.25 | 3.25 | 1.75 | 0.65 |
| APT7 | #2 | TWTY, 297, 5/8-1 | 0.25 | 3.25 | 1.78 | 0.65 |
| APT9 | 1/0 | TWTY, 297, 5/8-1 | 0.25 | 3.25 | 1.78 | 0.65 |
| APT10 | 2/0 | TX, 298, 840 | 0.31 | 4.22 | 2.28 | 0.91 |
| APT11 | 3/0 | TX, 298, 840 | 0.31 | 4.31 | 2.56 | 0.91 |
| APT12 | 4/0 | TX, 298, 840 | 0.38 | 4.22 | 2.28 | 0.91 |
| APT13 | 250 | TX, 298, 840 | 0.38 | 4.50 | 2.88 | 0.91 |
| APT15 | 350 | 1-1/8, 299 | 0.46 | 5.25 | 3.00 | 1.12 |
| APT18 | 500 | 106A, 300, 1-5/16 | 0.75 | 6.30 | 3.41 | 1.32 |
| APT23 | 750 | 125H, 608, 1-1/2 | 0.75 | 6.30 | 3.41 | 1.60 |
| APT28 | 1000 | 150H, 727, 1-3/4 | 0.88 | 6.30 | 3.41 | 1.84 |
Figure 1 is the standard shape, and Figure 2 is used for the -90 part numbers. B is the minimum dimension and the pin O.D. is the pin diameter, both in inches as Richards lists them. For other sizes, contact us.
| Part | Fig | Conductor | Die index | B min (in) | Pin O.D. (in) |
|---|---|---|---|---|---|
| CPT5 | 1 | #4 Cu stranded | 5/16, 8 | .82 | 0.250 |
| CPT9 | 1 | 1/0 Cu stranded | 1/2, 12 | .88 | 0.375 |
| CPT10 | 1 | 2/0 Cu stranded | 9/16, 13 | .94 | 0.375 |
| CPT12 | 1 | 4/0 Cu stranded | 5/8-1, 15 | 1.00 | 0.460 |
| CPT15 | 1 | 350 Cu stranded | 840, 18 | 1.12 | 0.562 |
| CPT18 | 1 | 500 Cu stranded | 1, 20 | 1.38 | 0.562 |
| CPT5-90 | 2 | #4 Cu stranded | 5/16, 8 | .81 | 0.375 |
| CPT9-90 | 2 | 1/0 Cu stranded | 1/2, 12 | .88 | 0.375 |
| CPT12-90 | 2 | 4/0 Cu stranded | 5/8-1, 15 | 1.00 | 0.460 |
| CPT15-90 | 2 | 350 Cu stranded | 840, 18 | 1.12 | 0.562 |
| CPT18-90 | 2 | 500 Cu stranded | 1, 20 | 1.38 | 0.562 |
Work through these checks before you order.
| Step | What to check |
|---|---|
| Conductor material | APT for aluminum or ACSR, CPT for copper |
| Cable size | Match the tables above, then confirm the die for your tool |
| Pin | Check the pin diameter against your lug or bushing, and the pin length (standard 6 in on the APT) |
| Shape | CPT Figure 1 is standard, Figure 2 is the -90 version |
Powertech Associates and Utility Power Supply Company represent Richards Manufacturing across New England and New York State. Linked parts are in our online store. For other sizes, dimensions or dies, contact Powertech Associates at info@powertech-upsc.com or (860) 678-8772.