Polywater Lubricant and Cable Jacket Compatibility: IEEE 1210, LSZH, CPE, CSPE and Polyethylene

November 11, 2026

Polywater Lubricant and Cable Jacket Compatibility: IEEE 1210, LSZH, CPE, CSPE and Polyethylene

Cable pulling lubricant touches the jacket for the life of the cable, so it has to be compatible with the jacket material. This guide covers how Polywater tests that compatibility, which jackets Polywater lists for each lubricant, and what to do when your jacket is not on the list. For product-by-product selection, see Polywater Cable Pulling Lubricants: How to Choose J, PJ, LZ, NN and More. Statements here are from Polywater's own product pages, technical data sheets, installation guide and knowledge hub.

How Compatibility Is Tested: IEEE 1210

IEEE 1210 is the standard test for determining compatibility of cable lubricants with wire and cable. Polywater helped develop it in 1996, and the second revision was approved in 2023, developed with the Canadian Standards Association.

Test elementWhat Polywater describes
AgingJacket material is aged in the lubricant, then tensile strength and elongation are compared to a control
Long testUnder IEEE 1210, a 30-day aging test is compared to a water-aged control
Short testA shorter high-temperature test is compared to both a water-aged and a non-aged control. The temperature follows NEMA/ICEA time-temperature requirements for the jacket's polymer group.
Polyethylene jacketsNEMA/ICEA aging is 2 days at 100 C, modified to include lubricant immersion. An Environmental Stress Crack Resistance (ESCR) test may also be run.
Electrical cablesDielectric breakdown or volume resistivity may also be tested after aging
RepeatsEach specimen is tested three times and averaged

Polywater is clear that no single test covers everything. Its article states, "There is no universal 1210 test." It also notes that water passes IEEE 1210 but is a poor pulling lubricant.

Jackets Polywater Lists, by Lubricant

These are the jacket materials Polywater states were aged in each lubricant and met the IEEE tensile and elongation retention requirements. A jacket missing from a row means the sheet does not list it, not that it fails.

LubricantFormJackets listed as meeting IEEE tensile and elongation requirementsStress cracking statement
Polywater JGelLLDPE, XLPE, CPE, PVC and EPRNo stress cracking on LDPE, LLDPE, MDPE or HDPE
Polywater PJPourableLLDPE, XLPE and PVCDoes not stress crack polyethylene
Polywater LZGelLSZH, CSPE, LLDPE, XLPE, CPE and PVCNo stress cracking on LDPE, MDPE or HDPE
Plus Silicone Type NNPourable gelLLDPE, HDPE, PP, XLPE, CPE and PVCNo stress cracking on LLDPE, MDPE or HDPE
Polywater CLRClear thick gelPVC, LLDPE and XLPENo stress cracking on LLDPE
Dyna-BlueThick gelXLPE, LLDPE, VLDPE, PVC, CPE and CSPENo stress cracking on LLDPE, MDPE or HDPE
Polywater SPYSprayable liquidLLDPE, XLPE and PVCNo stress cracking on LLDPE

The J, LZ, NN, CLR, Dyna-Blue and SPY rows come from Polywater technical data sheets. The PJ row comes from the PJ product page. Always check the current data sheet for your lubricant and cable.

Specialty Jackets: LSZH, CPE, CSPE, Fire-Rated and Plenum

Polywater points to one lubricant for these jackets.

LubricantPolywater statement
Polywater LZDesigned for LSZH/LSHF, CPE, CSPE, fire-rated and plenum jackets, and described as suitable on all cable jackets. Passes IEEE 1210, meets Telcordia GR-356-CORE and is UL Listed, including to Canadian safety standards.
Polywater PJPolywater states PJ is not recommended for LSZH/LSHF and certain CSPE and CPE cable jackets, and names LZ for those jackets.

Polywater's testing article shows why. In its LSZH tests, which covered 10 to 11 different blends at 50 C and 100 C, LZ was compatible with all blends tested, including at high temperature. Another lubricant it tested was compatible with some blends and not others. A wax-based lubricant softened one LSZH blend until it fell apart before testing, and a grease appeared to melt a different blend. A lubricant that was good on most jackets was incompatible with a CSPE blend at higher temperatures.

Cable Manufacturer Approvals

Polywater also lists cable manufacturers that have approved its pulling compounds for their cable jackets. The list is from a 2022 Polywater page and is not exhaustive. Polywater suggests asking your cable manufacturer whether it keeps its own approved lubricant list. The page does not say which lubricants each manufacturer approves.

Manufacturers listed by Polywater
Aetna Insulated Wire, Alcan Cable, American Insulated Wire, Brugg Cable, Conductores Monterrey (Viakon), Condumex, Draka Cableteq USA-BIW Cables, Elsewedy Cables, Encore Wire, General Cable/BICC Utility Prod, KEI Industries, LS Cable and Systems, Marmon Utility (Hendrix, Kerite), Nexans, NKT Cables, Okonite, Prysmian, Rockbestos Surprenant, Southwire, Sumitomo Electric, Superior Essex, Taihan Cable and Solutions

What Else Can Harm a Jacket

MaterialPolywater caution
Wax emulsionsCan negatively affect semi-conducting jackets, and can damage certain types of insulation and high voltage shields
Some soaps and waxesCan stress crack polyethylene jackets
Petroleum greases and oilsHarm many jacket materials
Added waterDo not add water to stretch the lubricant. It changes the friction and sidewall pressure.
Petroleum products and hot pipes near the cable routePolywater says leakage can harm the jacket, shield and insulation, and heat can accelerate aging

How to Check Your Jacket

StepWhat to do
1. Identify the jacketFind the jacket material on the cable data sheet: for example LLDPE, XLPE, PVC, CPE, CSPE or LSZH.
2. Check the lubricant sheetLook for your jacket in the table above and on the current Polywater data sheet for the lubricant.
3. Use LZ for specialty jacketsFor LSZH/LSHF, CPE, CSPE, fire-rated or plenum jackets, Polywater names LZ.
4. Ask the cable makerConfirm with your cable manufacturer, who may keep its own approved list.
5. Check the pullUse Pull-Planner to see the effect of a lubricant on tension and sidewall pressure.

Our Pull-Planner and lubricant calculator guide covers the planning tools, and the winter grade guide covers cold weather.

Frequently Asked Questions About Lubricant and Jacket Compatibility

What is IEEE 1210?

The standard test for determining compatibility of cable lubricants with wire and cable. Jacket material is aged in the lubricant and its tensile strength and elongation are compared to a control.

Which Polywater lubricant is for LSZH jackets?

Polywater LZ. Polywater states PJ is not recommended for LSZH/LSHF and certain CSPE and CPE jackets.

Is there one lubricant that works on every jacket?

Polywater describes LZ as suitable on all cable jackets, but it also says there is no universal 1210 test, so check the data sheet and your cable manufacturer.

Will Polywater lubricant stress crack polyethylene?

Polywater states that LZ, PJ and its other listed lubricants do not stress crack the polyethylene types listed on their sheets. See the table above for each.

Do cable manufacturers approve Polywater lubricants?

Polywater lists 22 cable manufacturers that approve its pulling compounds. Ask your cable manufacturer which specific lubricants it approves.

Can I add water to stretch a lubricant?

No. Polywater says water should not be added to increase lubricant quantity.

Is the compatibility list the same for winter grades?

Polywater lists WJ, WPJ, WLZ and WNN as the winter versions of J, PJ, LZ and NN. Check the winter grade data sheet for your jacket.

Where to Buy Polywater Lubricants

Powertech Associates supplies Polywater cable pulling lubricants. Order online: J-128, PJ-128, LZ-128, NN-128, CLR-128, D-128 Dyna-Blue or SPY-128. For help matching a lubricant to your cable jacket, contact Powertech Associates at info@powertech-upsc.com or (860) 678-8772. Always check the current Polywater data sheet and your cable manufacturer's approvals.

Last updated: November 2026.

Interested in this product?

Contact us, request a quote, or order online.