Splicing medium voltage cable comes down to one early decision: heat shrink or cold applied. After that you match the splice to your voltage class, cable type, conductor size and insulation diameter. This guide covers the TE Connectivity Raychem in-line splices we stock and what each one is built for.
TE makes both and says the choice depends on the technical needs of the project.
| Heat shrink | Cold shrink (cold applied) | |
|---|---|---|
| How it works | Cross-linked polymer tubes shrink to the cable when heated. TE has made heat shrink for more than 50 years | Silicone or EPDM sleeve pre-expanded on a spiral holdout. You pull out the holdout and it recovers onto the cable |
| Materials | EVA and polyolefin, rigid and tough | Silicone and EPDM rubber, flexible |
| Install | Multi-layer tubing installed in minutes with a gas torch. Visual indicators show correct installation | Design minimizes installation steps, no torch |
| Voltage range (per TE, for the technology overall) | LV, MV and HV up to 72 kV | LV, MV and HV up to 245 kV |
| Field record (per TE) | 40+ years without maintenance | 15 years of proven field service |
| Best when | You want a long track record and adaptability to out-of-round or out-of-spec cable | A torch is restricted, or space is tight |
| Connectors | Accepts shear-bolt or compression | Accepts shear-bolt or compression |
The voltage ranges above are TE's for each technology as a whole. The Raychem heat shrink (HVS) splices we stock cover 5 to 35 kV, and the CSJA cold shrink joint covers 15 to 35 kV.
TE's own bottom line: heat shrink offers a wide range of connections with proven longevity and a lower total cost of ownership, and cold applied is especially good where gas torch use is restricted or space is constricted. Both resist UV, pollution, chemicals, salt fog and tracking, and both can be built to flame retardant requirements.
The CSJA is an all-in-one in-line joint for 15 to 35 kV single conductor shielded cable. It splices tape shield, wire shield, LC shield, UniShield, JCN and flat strap cables. The one-piece silicone rubber body has factory-molded stress cones and a Faraday cage, so no void-filling stress relief mastic is needed. A pre-expanded EPDM rejacketing splice and integrated neutral sock are part of the kit, and the shield continuity design can bridge concentric neutrals.
The ergonomic spiral holdout releases with low force, and the splice body is 14 to 19 inches long on the holdout. With a shear-bolt connector it is a crimpless system. Each splice body is factory tested for AC withstand and partial discharge under IEEE 404, and the design meets IEEE 404 for 15 to 35 kV. More in our CSJA write-up.
CSJA 1522-2822 cold shrink splice for single core polymeric insulated (XLPE-EPR) cables up to 35kV
| Catalog # | Voltage | Conductor (AWG/kcmil) | Insulation OD (in) |
|---|---|---|---|
| CSJA-1521M4 | 15 kV | #2 to 3/0 | 0.69 to 1.20 |
| CSJA-1521M5 | 15 kV | #2 to 350 | 0.69 to 1.20 |
| CSJA-1522M6 | 15 kV | 4/0 to 500 | 0.87 to 1.40 |
| CSJA-1522M7 | 15 kV | 500 to 750 | 0.87 to 1.40 |
| CSJA-1523M8 | 15 kV | 350 to 750 | 1.03 to 1.58 |
| CSJA-1524M9 | 15 kV | 750 to 1000 | 1.28 to 2.05 |
| CSJA-2822M5 | 28 kV | #1 to 350 | 0.87 to 1.40 |
| CSJA-2822M6 | 28 kV | 4/0 to 500 | 0.87 to 1.40 |
| CSJA-2823M8 | 28 kV | 350 to 750 | 1.03 to 1.58 |
| CSJA-2824M8 | 28 kV | 500 to 750 | 1.28 to 2.05 |
| CSJA-2824M9 | 28 kV | 750 to 1000 | 1.28 to 2.05 |
| CSJA-3523M5 | 35 kV | 1/0 to 350 | 1.03 to 1.49 |
| CSJA-3524M8 | 35 kV | 350 to 750 | 1.36 to 2.05 |
| CSJA-3524M9 | 35 kV | 750 to 1000 | 1.36 to 2.05 |
| CSJA-3525M10 | 35 kV | 1000 to 1250 | 1.63 to 2.36 |
The CSJA-1521M0 is the copper connector version (#2 to 4/0). Kits with an M0 to M3 number use a copper connector and M4 to M10 use aluminum. CSJA joints are also made without a connector (CSJA-1521 through 3525). For external grounding, TE offers the CSJ-EG-1, -2 and -3 kits with 24 in of moisture blocked braid in #8, #6 and #4. Order by insulation OD and jacket OD first, then confirm the connector against the conductor diameter.
TE's Raychem heat shrink joint line covers in-line splices, transition splices, tap splices and armored cable splices. All of them are installed with a torch, and we compare the options in our Raychem torches and accessories guide. TE says the HVS 1/C splice is suitable for connections in permanent water such as flooded vaults and manholes.
| Family | What it is for | Voltage | Kits in our store |
|---|---|---|---|
| HVS 1/C | In-line splice for single conductor shielded cable, with solderless grounding kit | 5 to 35 kV | HVS-821S to 825S, HVS-1521S to 1525S (also with a -W wraparound sleeve), HVS-2521S to 2523S and HVS-3521S to 3523S. Every size is in the in-line table below |
| HVS-J | In-line splice for 1/C jacketed concentric neutral cable, with an MBSM wraparound outer jacket | 25, 28 and 35 kV | HVS-2511E-J to 2513E-J and HVS-3511S-J to 3513S-J. Sizes are in the HVS-J table below |
| HVS with connector | 15 kV splice with a connector in the kit | 15 kV | Aluminum shear-bolt: HVS-S-1522S-M4, M5, 1523S-M6, 1524S-M8, M9. Copper: HVS-C-1522S-M1, 1523S-M2. Sizes are in the HVS-S and HVS-C tables below |
| HVS D and E series | In-line splices for PILC or VCLC cable, or transition splices from PILC/VCLC to poly cable. Sizes are in the HVS D and E series table below | 5, 15, 25 and 35 kV | HVS-582D, HVS-1581D, 1582D, 1583D, 1584D, 1585DNS, HVS-2582E, 2583E, 2584E, HVS-3582D, 3583D, 3584D |
| HVS-T and HVSR-T transition | Splices one three-core PILC cable to three one-core polymeric cables | up to 15, 25 and 35 kV | 17 kits, all listed with sizes in the transition table below |
| HVSR transition reducer | Transition splice with a reducing design | 15 and 25 kV | HVSR-1582, 1583, 1584, 2583E, 2584E |
| HVSY | WYE tap splice for 1/C poly-poly, PILC-PILC and PILC-poly cable | up to 15 kV | HVSY-1522S, HVSY-1523S |
| HVSA-3 | In-line splice for 3/C armored cable (SWA, STA, steel corrugated or aluminum armor) | 5 to 15 kV | HVSA-3-821S to 825S and HVSA-3-1521S to 1524S. Sizes in the armored table below |
| HVSA MOD kits | Rearmoring and rejacketing kits for 3/C armored cable | 5 to 35 kV | HVSA-1-MOD, HVSA-2-MOD, HVSA-3-MOD, HVSA-4-MOD |
Start with the part number you were quoted or have on a truck list. Each row says what the kit splices and whether you need to buy a connector separately. Insulation OD is in inches for the HVS-C kits and millimeters for the rest, as TE prints them.
| Catalog # | Voltage | Conductor (AWG/kcmil) | Insulation OD | What it splices | Connector in kit |
|---|---|---|---|---|---|
| HVS-C-1522S | 15 kV | 3/0 to 400 | 0.85 to 1.30 in | Single conductor in-line | No, order a compression connector separately |
| HVS-C-1522S-M1 | 15 kV | 3/0 to 400 | 0.85 to 1.30 in | Single conductor in-line | Yes, copper shear bolt CSBS-20C-500C-SOS |
| HVS-C-1523S | 15 kV | 500 to 750 | 1.10 to 1.55 in | Single conductor in-line | No, order a compression connector separately |
| HVS-C-1523S-M2 | 15 kV | 500 to 750 | 1.10 to 1.55 in | Single conductor in-line | Yes, copper shear bolt CSBS-300C-750C-SOS |
| HVS-T-1581S | 15 kV | 4 to 4/0 | PILC 15.24 to 25.4, poly 16.51 to 26.67 mm | 3-core PILC to three 1-core polymeric | No, see transition table below |
| HVS-T-1582S | 15 kV | 250 to 350 | PILC 21.59 to 27.94, poly 22.86 to 33.02 mm | 3-core PILC to three 1-core polymeric | No, see transition table below |
| HVS-T-1583S | 15 kV | 500 to 750 | PILC 26.67 to 38.1, poly 27.94 to 40.64 mm | 3-core PILC to three 1-core polymeric | No, see transition table below |
| HVSY-1522S | 15 kV | 2 to 4/0 main and tap | 16.51 to 26.67 mm | Wye tap | No, see wye tap table below |
| HVSY-1523S | 15 kV | 250 to 750 main, 2 to 750 tap | Main 24.13 to 36.83, tap 16.51 to 36.83 mm | Wye tap | No, see wye tap table below |
Kit with or without the connector. TE says the HVS-C-1521S to 1524S kits need a separately ordered compression connector. Only the -M1 and -M2 kits include a connector, a copper shear bolt connector, and TE says those are the only two connector kits. The aluminum shear-bolt version is the HVS-S line, for example HVS-S-1522S-M4. For external grounding, order an HVS-EG kit. If you are not sure which kit your job needs, contact Powertech Associates before ordering.
Sizing check. Measure the conductor and the insulation OD, then pick the row where both fit. If the cable is outside the range, the HVS-SHIM kits cover it. Contact us before ordering a shim.
For single conductor shielded cable. Insulation OD in millimeters, from TE's data. The 15 kV kits are also sold with a -W wraparound rejacketing sleeve at the same sizes, linked after the standard kit. Part numbers without a link are TE catalog items we can order on request. The jacketed concentric neutral kits (HVS-J) have their own table further down.
| Catalog # | Voltage | Conductor (AWG/kcmil) | Insulation OD (mm) |
|---|---|---|---|
| HVS-821S | 8 kV | 6 to 2 | 8.89 to 16.51 |
| HVS-822S | 8 kV | 1 to 4/0 | 13.97 to 22.86 |
| HVS-823S | 8 kV | 250 to 350 | 13.97 to 22.86 |
| HVS-824S | 8 kV | 500 to 750 | 25.4 to 40.64 |
| HVS-825S | 8 kV | 750 to 1000 | 33.02 to 57.15 |
| HVS-1521S / -W | 15 kV | 2 to 4/0 | 16.51 to 26.67 |
| HVS-1522S / -W | 15 kV | 250 to 350 | 22.86 to 33.02 |
| HVS-1523S / -W | 15 kV | 500 to 750 | 27.94 to 40.64 |
| HVS-1524S / -W | 15 kV | 750 to 1000 | 31.75 to 45.72 |
| HVS-1525S / -W | 15 kV | 1250 to 2000 | 40.64 to 63.5 |
| HVS-2521S | 25 kV | 1 to 250 | 22.86 to 30.48 |
| HVS-2522S | 25 kV | 350 to 500 | 30.48 to 38.1 |
| HVS-2523S | 25 kV | 750 to 1000 | 38.1 to 45.72 |
| HVS-3521S | 35 kV | 1/0 to 3/0 | 24.13 to 34.3 |
| HVS-3522S | 35 kV | 4/0 to 600 | 30.48 to 43.18 |
| HVS-3523S | 35 kV | 600 to 1000 | 39.37 to 54.61 |
TE's HVS-J catalog page covers these 25, 28 and 35 kV kits for 1/C jacketed concentric neutral cable. Sizes are in inches with millimeters in parentheses. TE says the kits do not contain connectors, so order compression or solder connectors separately. If you need external grounding or shield interruption, order an HVS-EG kit. Nominal insulation thickness (100%): 25 kV 260 mils, 28 kV 280 mils, 35 kV 345 mils. One kit per box. TE test reports: 25 kV EDR-5150, 28 kV EDR-5318, 35 kV EDR-5157.
| Catalog # | Voltage | Conductor (AWG/kcmil) | Insulation OD (in.) | Max jacket OD (in.) | Max connector OD (in.) | Max connector length (in.) | Installed kit length (in.) | Required space (in.) |
|---|---|---|---|---|---|---|---|---|
| HVS-2511E-J | 25/28 kV | #1 to 250 | 0.90 to 1.20 (23 to 30) | 1.55 (39) | 1.10 (28) | 4.0 (102) | 40 (1016) | 56 (1422) |
| HVS-2512E-J | 25/28 kV | 350 to 500 | 1.20 to 1.50 (30 to 38) | 1.95 (50) | 1.35 (34) | 6.0 (152) | 48 (1219) | 68 (1727) |
| HVS-2513E-J | 25/28 kV | 750 to 1000 | 1.50 to 1.80 (38 to 46) | 2.40 (61) | 1.85 (47) | 8.0 (203) | 48 (1219) | 70 (1778) |
| HVS-3511S-J | 35 kV | 1/0 to 3/0 | 0.95 to 1.35 (24 to 34) | 1.55 (39) | 1.00 (25) | 5.0 (127) | 44 (1118) | 53 (1346) |
| HVS-3512S-J | 35 kV | 4/0 to 500 | 1.20 to 1.70 (30 to 43) | 2.10 (53) | 1.60 (41) | 8.0 (203) | 48 (1219) | 63 (1600) |
| HVS-3513S-J | 35 kV | 600 to 1000 | 1.55 to 2.15 (39 to 55) | 2.80 (71) | 1.85 (47) | 10.0 (254) | 48 (1219) | 64 (1626) |
TE's HVS/HVSR 1/C data sheet (E575, 10/2014) covers these 15, 25 and 35 kV kits. They splice paper-insulated lead-covered (PILC) or varnished cambric lead-covered (VCLC) cable in-line, or transition from PILC/VCLC to poly cable (copper tape, lead sheath, wire shield, UniShield, or jacketed or unjacketed concentric neutral). The PILC splices use oil-stop systems, and the kits are tested to the electrical and load cycling requirements of IEEE 404. Sizes below are TE's, in inches with millimeters converted. Connector lengths are shown as PILC to PILC / PILC to poly.
| Catalog # | Voltage | PILC/poly conductor (AWG/kcmil) | PILC insulation (in.) | Poly insulation (in.) | Connector OD | Connector length (in.) | Installed kit length (in.) | Required space (in.) |
|---|---|---|---|---|---|---|---|---|
| HVS-1581D | 15 kV | 4 to 4/0 | 0.60 to 0.90 (15 to 23 mm) | 0.65 to 1.05 (17 to 27 mm) | 0.90 (23 mm) | 3.5 / 4.5 | 31 | 48 |
| HVS-1582D | 15 kV | 250 to 350 | 0.85 to 1.10 (22 to 28 mm) | 0.90 to 1.30 (23 to 33 mm) | 1.15 (29 mm) | 3.5 / 5.5 | 35 | 50 |
| HVS-1583D | 15 kV | 500 to 750 | 1.05 to 1.30 (27 to 33 mm) | 1.10 to 1.60 (28 to 41 mm) | 1.60 (41 mm) | 5.0 / 7.0 | 37 | 50 |
| HVS-1584D | 15 kV | 750 to 1000 | 1.15 to 1.50 (29 to 38 mm) | 1.25 to 1.80 (32 to 46 mm) | 1.85 (47 mm) | 6.0 / 8.0 | 40 | 54 |
| HVS-2582E | 25 kV | 1 to 250 | 0.85 to 1.20 (22 to 30 mm) | 0.90 to 1.25 (23 to 32 mm) | 1.10 (28 mm) | 3.5 / 4.5 | 40 | 57 |
| HVS-2583E | 25 kV | 350 to 500 | 1.15 to 1.45 (29 to 37 mm) | 1.15 to 1.50 (29 to 38 mm) | 1.35 (34 mm) | 5.0 / 8.0 | 40 | 58 |
| HVS-2584E | 25 kV | 750 to 1000 | 1.50 to 1.70 (38 to 43 mm) | 1.60 to 1.90 (41 to 48 mm) | 1.85 (47 mm) | 6.0 / 9.0 | 40 | 61 |
| HVS-3582D | 35 kV | 1/0 to 250 | 1.05 to 1.40 (27 to 36 mm) | 1.05 to 1.40 (27 to 36 mm) | 1.20 (30 mm) | 3.5 / 5.5 | 40 | 62 |
| HVS-3583D | 35 kV | 300 to 750 | 1.20 to 1.70 (30 to 43 mm) | 1.30 to 1.75 (33 to 44 mm) | 1.60 (41 mm) | 6.0 / 9.0 | 48 | 67 |
| HVS-3584D | 35 kV | 750 to 1000 | 1.60 to 2.00 (41 to 51 mm) | 1.65 to 2.00 (42 to 51 mm) | 1.85 (47 mm) | 7.0 / 10.0 | 48 | 67 |
The HVSR kits are for a transition when the PILC or VCLC conductor is much smaller than the poly cable conductor. They only splice PILC to poly, so TE lists one connector length.
| Catalog # | Voltage | Conductors (AWG/kcmil) | PILC insulation (in.) | Poly insulation (in.) | Connector OD | PILC to poly connector length (in.) | Installed kit length (in.) | Required space (in.) |
|---|---|---|---|---|---|---|---|---|
| HVSR-1582 | 15 kV | PILC #4 to 4/0, poly 4/0 to 350 | 0.60 to 0.90 (15 to 23 mm) | 0.90 to 1.30 (23 to 33 mm) | 1.15 (29 mm) | 5.5 | 33 | 78 |
| HVSR-1583 | 15 kV | PILC 4/0 to 350, poly 500 to 750 | 0.80 to 1.10 (20 to 28 mm) | 1.10 to 1.60 (28 to 41 mm) | 1.60 (41 mm) | 7.0 | 37 | 87 |
| HVSR-1584 | 15 kV | PILC 4/0 to 500, poly 750 to 1000 | 0.80 to 1.20 (20 to 30 mm) | 1.25 to 1.80 (32 to 46 mm) | 1.85 (47 mm) | 8.0 | 40 | 92 |
| HVSR-2583E | 25 kV | PILC #1 to 350, poly 350 to 500 | 0.80 to 1.20 (20 to 30 mm) | 1.15 to 1.50 (29 to 38 mm) | 1.35 (34 mm) | 7.0 | 40 | 58 |
| HVSR-2584E | 25 kV | PILC 500 to 750, poly 750 to 1000 | 1.25 to 1.50 (32 to 38 mm) | 1.55 to 1.90 (39 to 48 mm) | 1.85 (47 mm) | 8.0 | 40 | 61 |
TE says these kits do not contain ShearBolt connectors, so order oil block connectors (sweated or compression) separately. For lead sheath repair, order an HVS-LR kit. Selections are based on typical dimensions of 100% and 133% insulated cables and commonly used connectors, using AEIC nominal insulation thickness. One kit per box. TE test reports: 15 kV EDR-5080, 25 kV EDR-5083, 28 kV EDR-5318 and 35 kV EDR-5184.
PILC and VCLC splices start with removing the paper insulation. TE lists the EXRM-1004 insulation stripping pliers for paper insulated cables. They are 190 mm long and cover 15 to 50 mm cable OD. The TE part number is 702607N001. TE's Energy Accessories catalog (EPP-2443, 10/15) also lists the EXRM-0764 insulation stripping string for plastic insulated cable. Contact Powertech Associates to order the string.
15 kV in-line splices from the HVS-C family. Insulation OD in millimeters. The -M1 and -M2 kits at the end include a copper shear bolt connector.
| Catalog # | Voltage | Conductor (AWG/kcmil) | Insulation OD (mm) |
|---|---|---|---|
| HVS-C-1521S | 15 kV | 2 to 2/0 | 16.51 to 24.13 |
| HVS-C-1522S | 15 kV | 3/0 to 400 | 21.59 to 33.02 |
| HVS-C-1523S | 15 kV | 500 to 750 | 28 to 39.37 |
| HVS-C-1524S | 15 kV | 750 to 1000 | 33.02 to 48.26 |
| HVS-C-1522S-M1 | 15 kV | 3/0 to 400 | 21.59 to 33.02 |
| HVS-C-1523S-M2 | 15 kV | 500 to 750 | 28 to 39.37 |
15 kV in-line splices with an aluminum mechanical shear-bolt connector included. Insulation OD in millimeters, converted from TE's inch values. The connector in each kit is listed in the last column.
| Catalog # | Voltage | Conductor (AWG/kcmil) | Insulation OD (mm) | Connector in kit |
|---|---|---|---|---|
| HVS-S-1522S-M4 | 15 kV | 2 to 2/0 | 16.51 to 24.13 | ASBS-2-3/0 |
| HVS-S-1522S-M5 | 15 kV | 2/0 to 350 | 20.07 to 30.23 | ASBS-2-350 |
| HVS-S-1523S-M6 | 15 kV | 350 to 500 | 26.42 to 33.78 | ASBS-3/0-500 |
| HVS-S-1524S-M8 | 15 kV | 500 to 750 | 29.46 to 39.37 | ASBS-500-750 |
| HVS-S-1524S-M9 | 15 kV | 750 to 1000 | 34.29 to 43.18 | ASBS-600-1000 |
For splicing three-core PILC cable to three one-core polymeric cables. Insulation diameters are listed for the PILC cable and the poly cable, and jacket OD is the maximum, all in millimeters converted from TE's inch values. These kits do not include connectors, so order oil block connectors (sweated or compression) separately. The HVSR-T kits are for a PILC conductor much smaller than the poly conductor, so their conductor column shows PILC first, then poly.
| Catalog # | Voltage | Conductor (AWG/kcmil) | PILC insulation (mm) | Poly insulation (mm) | Max jacket OD (mm) |
|---|---|---|---|---|---|
| HVS-T-1581S | 15 kV | 4 to 4/0 | 15.24 to 25.4 | 16.51 to 26.67 | 34.29 |
| HVS-T-1581E-S | 15 kV | 1/0 to 4/0 | 16.51 to 25.4 | 17.78 to 26.67 | 35.56 |
| HVS-T-1582S | 15 kV | 250 to 350 | 21.59 to 27.94 | 22.86 to 33.02 | 38.1 |
| HVS-T-1582E-S | 15 kV | 250 to 500 | 21.59 to 30.48 | 22.86 to 30.48 | 38.1 |
| HVS-T-1583S | 15 kV | 500 to 750 | 26.67 to 38.1 | 27.94 to 40.64 | 48.26 |
| HVS-T-1583E-S | 15 kV | 500 to 1000 | 27.94 to 38.1 | 29.21 to 44.45 | 55.88 |
| HVS-T-1584S | 15 kV | 750 to 1000 | 33.02 to 44.45 | 31.75 to 45.72 | 54.61 |
| HVSR-T-1582 | 15 kV | Contact us | 15.24 to 25.4 | 22.86 to 33.02 | 38.1 |
| HVSR-T-1583 | 15 kV | PILC 4/0 to 350, poly 500 to 750 | 20.32 to 30.48 | 27.94 to 40.64 | 48.26 |
| HVSR-T-1584 | 15 kV | PILC 250 to 500, poly 750 to 1000 | 21.59 to 33.02 | 31.75 to 45.72 | 54.61 |
| HVS-T-2582E | 25 kV | 1/0 to 250 | 21.59 to 30.48 | 22.86 to 31.75 | 39.37 |
| HVS-T-2583E | 25 kV | 350 to 500 | 29.21 to 35.56 | 29.21 to 38.1 | 50.8 |
| HVS-T-2584E | 25 kV | 750 to 1000 | 38.1 to 43.18 | 38.1 to 48.26 | 54.61 |
| HVSR-T-2582E | 25 kV | PILC #1 to 400, poly 350 to 500 | 20.32 to 30.48 | 29.21 to 38.1 | 50.8 |
| HVSR-T-2583E | 25 kV | PILC 500 to 600, poly 750 to 1000 | 31.75 to 35.56 | 39.37 to 48.26 | 54.61 |
| HVS-T-3582S | 35 kV | 1/0 to 350 | 26.67 to 35.56 | 26.67 to 38.1 | 48.26 |
| HVS-T-3583S | 35 kV | 250 to 750 | 30.48 to 43.18 | 33.02 to 44.45 | 53.34 |
Welcome to TE's Raychem HVS-T heat shrink splice installation video. We will be splicing a 15 KV three conductor paper insulated lead covered cable (PILC) to 3ea 15 KV single conductor extruded dielectric Flat Strap shielded power cable.
For 15 kV wye taps on single conductor poly cable. Insulation OD in millimeters, converted from TE's inch values. These kits do not include connectors. The first two rows are for soldered connectors. The rest are for Burndy YSH crimp connectors, which work on copper conductors only. For an H configuration on 1/C shielded cable, TE says to add an HVSH-1520 mod kit.
| Catalog # | Connector type | Main conductor | Tap conductor | Main insulation (mm) | Tap insulation (mm) |
|---|---|---|---|---|---|
| HVSY-1522S | Soldered | 2 to 4/0 | 2 to 4/0 | 16.51 to 26.67 | 16.51 to 26.67 |
| HVSY-1523S | Soldered | 250 to 750 | 2 to 750 | 24.13 to 36.83 | 16.51 to 36.83 |
| HVSY-1522S | Burndy YSH-2929 (copper) | 2 to 4/0 | 2 to 4/0 | 16.51 to 26.67 | 16.51 to 26.67 |
| HVSY-1523S | Burndy YSH-3434 (copper) | 250 to 500 | 4/0 to 500 | 21.59 to 31.75 | 21.59 to 31.75 |
| HVSY-1523S | Burndy YSH-3939 (copper) | 500 to 750 | 350 to 750 | 27.94 to 36.83 | 25.4 to 36.83 |
For three-core armored cable. Insulation OD in millimeters, converted from TE's inch values. TE lists the 8 kV kits with a conductor range for 5 kV cable and another for 8 kV cable, and says to consult TE above 15 kV. These kits do not include connectors, so order compression or solder connectors separately. If you need external grounding or shield interruption, TE says to add an HVS-EG-3 kit.
| Catalog # | Voltage | Conductor (AWG/kcmil) | Insulation OD (mm) |
|---|---|---|---|
| HVSA-3-821S | 5 and 8 kV | 5 kV: 6 to 2/0. 8 kV: 6 to 2 | 8.89 to 16.51 |
| HVSA-3-822S | 5 and 8 kV | 5 kV: 3/0 to 300. 8 kV: 1 to 4/0 | 13.97 to 22.86 |
| HVSA-3-823S | 5 and 8 kV | 5 kV: 350 to 750. 8 kV: 250 to 350 | 20.32 to 31.75 |
| HVSA-3-824S | 5 and 8 kV | 5 kV: 1000 to 1500. 8 kV: 500 to 750 | 25.4 to 40.64 |
| HVSA-3-825S | 8 kV | 750 to 1000 | 33.02 to 57.15 |
| HVSA-3-1521S | 15 kV | 2 to 4/0 | 16.51 to 26.67 |
| HVSA-3-1522S | 15 kV | 250 to 350 | 22.86 to 33.02 |
| HVSA-3-1523S | 15 kV | 500 to 750 | 27.94 to 40.64 |
| HVSA-3-1524S | 15 kV | 750 to 1000 | 31.75 to 45.72 |
When the shield or ground connection has to be carried past the splice, TE offers HVS-EG kits. We don't keep these in stock, but we can order any of the six for you. EG-1 to EG-3 are for single conductor cable with a 24 in moisture-blocked braid, and EG-3-1 to EG-3-3 are for three conductor cable with a 36 in braid. Pick the kit by the insulation diameter of your cable.
| Catalog # | Cable | Insulation diameter | Moisture-blocked braid | Braid (AWG) |
|---|---|---|---|---|
| HVS-EG-1 | 1/C | 0.30 to 1.25 in (8 to 32 mm) | 24 in (610 mm) | #8 |
| HVS-EG-2 | 1/C | 1.00 to 2.15 in (25 to 55 mm) | 24 in (610 mm) | #6 |
| HVS-EG-3 | 1/C | 1.55 to 3.40 in (39 to 86 mm) | 24 in (610 mm) | #4 |
| HVS-EG-3-1 | 3/C | 0.30 to 1.25 in (8 to 32 mm) | 36 in (914 mm) | #8 |
| HVS-EG-3-2 | 3/C | 1.00 to 2.15 in (25 to 55 mm) | 36 in (914 mm) | #6 |
| HVS-EG-3-3 | 3/C | 1.55 to 3.40 in (39 to 86 mm) | 36 in (914 mm) | #4 |
Start with what you are splicing, then use the kit family to find the right size table above.
| What you are splicing | Kit family | Voltage | Notes |
|---|---|---|---|
| Single conductor shielded cable, torch allowed | HVS 1/C (HVS-821S to 3523S) | 5 to 35 kV | Fits out-of-round and out-of-spec cable. Connector ordered separately |
| Single conductor shielded cable, torch restricted or tight space | CSJA cold shrink joint | 15 to 35 kV | No torch. M-number kits include a connector |
| Single conductor 15 kV with the connector in the kit | HVS-S (aluminum shear-bolt) or HVS-C (copper) with an M number | 15 kV | HVS-C-1521S to 1524S are the no-connector kits |
| Jacketed concentric neutral cable | HVS-J (HVS-2511E-J to 3513S-J) | 25, 28 and 35 kV | MBSM wraparound outer jacket. Connector ordered separately. Sizes in the HVS-J table |
| PILC or VCLC cable, in-line or transition to poly | HVS D and E series | 15, 25 and 35 kV | Match conductor and PILC and poly insulation. Sizes in the D and E series table |
| Three-core PILC to three single-core polymeric | HVS-T and HVSR-T | 15, 25 and 35 kV | Match conductor, PILC and poly insulation, and jacket OD |
| Transition with a reducing design | HVSR | 15 and 25 kV | PILC conductor much smaller than the poly conductor. Sizes in the HVSR table |
| Branch or tap off a main cable | HVSY wye tap | Up to 15 kV | For 1/C poly-poly, PILC-PILC and PILC-poly |
| Three-core armored cable | HVSA-3 | 5 to 15 kV | Rebuilds the armor and seals with a wraparound |
| Rearmoring or rejacketing armored cable | HVSA-1-MOD to 4-MOD | 5 to 35 kV | Used with the armored cable splices |
| Carrying the shield or ground past the splice | HVS-EG kits | n/a | EG1, EG2, EG3 and the EG-3 variants. Available to order |
| Cable diameter outside the kit range | HVS-SHIM 1 through 6 | n/a | Contact us before ordering |
Neither wins every job. TE makes both. Cold shrink suits places where torches are restricted and gives a compact one-piece design. Heat shrink has the longer track record and adapts to out-of-round cable.
Kits with an M number do. M0 to M3 are copper and M4 to M10 are aluminum.
Only the HVS-S and HVS-C kits with an M number. The standard HVS kits are sold without one.
TE lists the CSJA, HVS 1/C, HVS-J, HVSY and HVSA-3 families as qualified to or meeting IEEE 404.
Yes, with a transition kit. The HVS-T and HVSR-T kits splice a three-core PILC cable to three one-core polymeric cables.
HVS-SHIM kits extend the range for cable outside the standard diameters. Contact us before ordering.
It depends on the size of the splice. Our Raychem torches and accessories guide compares the three Raychem torch kits and the hoses and regulators that go with them.
Powertech Associates and Utility Power Supply Company represent TE Connectivity across New England and New York State. Tell us the voltage, cable type and conductor size and we will help you pick the kit. Contact us at info@powertech-upsc.com or (860) 678-8772.
Last updated: November 2026.