Raychem RDSS Duct Sealing System: Sizes, Clips and Installation Tools

September 15, 2019

Raychem RDSS Duct Sealing System: Sizes, Clips and Installation Tools

The Raychem RDSS (Rayflate Duct Sealing System) from TE Connectivity is an inflatable duct seal for power cable ducts. A flexible plastic laminate bladder with high-temperature sealant strips on both sides wraps around the cable or cables. Inflated to about 45 psi (3 bar), it presses the sealant against the duct wall and the cable jacket to make a watertight seal, and a self-sealing gel valve closes the fill hole when the filling tube comes out. TE lists it for plastic, steel and concrete ducts, in dry or wet conditions.

RDSS at a Glance

ItemWhat TE lists
SealFlexible laminate bladder with high-temperature sealant strips on both sides
Inflation3.0 +/- 0.2 bar (about 45 psi), with a hand inflator that has a gauge and pressure limiter
Fill holeSelf-sealing gel valve prevents pressure loss once the filling tube is removed
Installation conditionDry or wet, including a duct with water still flowing through it
Duct systemsConcrete, plastic or steel
Duct shapeIndependent of duct ovality
CablesEmpty ducts, or ducts with one or more cables, with different cable diameters allowed in the same duct
Test reportEDR-5253
DrawingEPD-202-312007-01 (TE says to use it for all design work)

What TE Tested

TE's RDSS catalog (EPP-0569) describes these tests. The detailed test report is available from TE on request.

TestResult TE lists
Water and gas tightnessWater tight and gas tight at up to 0.3 bar (a 3 m water column) at room temperature, including with the cables under vibration, bending, torsion, pull and push
Chemical and bacterial resistancePassed
Load cyclingTested with a conductor temperature of 90 degrees C, following VDE 0278 Part 1, for use on high current cables
Empty and multi-cable ductsWater and gas tight at 0.3 bar
Service lifeCalculations show the seals still hold 0.3 bar of a 3 m water column after 30 years, based on a typical daily utility load cycle at 25 degrees C ambient and diffusion measurements at elevated temperatures

RDSS Sizing Chart

These are the admissible cable diameters, in mm, that TE lists for each kit by duct inside diameter. For a bundle of cables, use the diameter of the bundle. A dash means the kit does not cover that duct size.

Duct ID (mm)RDSS-45RDSS-60RDSS-75RDSS-100RDSS-125RDSS-150
32.50 - 14-----
350 - 18-----
400 - 27-----
450 - 320 - 18----
50-0 - 30----
55-0 - 380 - 28---
60-0 - 450 - 30---
65--0 - 40---
70--0 - 46---
75--0 - 560 - 45--
80---0 - 52--
85---0 - 60--
90---0 - 66--
95---0 - 74--
100---0 - 800 - 65-
105---0 - 850 - 75-
110---0 - 900 - 83-
115---55 - 95*0 - 91-
120---60 - 100*0 - 95-
125----0 - 10360 - 100
130----70 - 110*60 - 107
135----75 - 115*60 - 112
140----80 - 120*60 - 118
145----85 - 125*60 - 123
150----90 - 130*60 - 129
155-----60 - 134*
160-----60 - 139*
165-----105 - 145*
170-----110 - 150*
175-----115 - 155*
180-----120 - 160*

An asterisk means an RDSS-CLIP must be used even with only two cables. For duct sizes over 180 mm, ask TE. Each RDSS element can seal an empty duct (except the RDSS-150, where TE offers empty-duct sealing on request) or a duct with up to two cables. The RDSS-100 at 115 and 120 mm, the RDSS-125 at 130 to 150 mm, and the RDSS-150 are for ducts with cable only. TE's catalog pairs the RDSS-AD-210 adapter with the RDSS-125 and RDSS-150.

RDSS-100 Sizing by Number of Cables

The RDSS-100 cut sheet gives the maximum cable bundle diameter by duct size and cable count. TE's catalog says to subtract 5 mm from the chart value for each clip used. Measure the bundle with a diameter tape, or ask TE.

Duct ID0 to 2 cables3 to 4 cables (1 clip)5 to 7 cables (2 clips)
3.25 in. (83 mm)2.2 in. (56 mm)2.0 in. (50 mm)1.8 in. (46 mm)
3.50 in. (89 mm)2.6 in. (66 mm)2.4 in. (61 mm)2.2 in. (56 mm)
3.75 in. (95 mm)2.9 in. (74 mm)2.7 in. (69 mm)2.5 in. (64 mm)
4.00 in. (100 mm)3.2 in. (80 mm)3.0 in. (75 mm)2.8 in. (70 mm)
4.25 in. (108 mm)3.5 in. (89 mm)3.3 in. (85 mm)3.1 in. (79 mm)
4.50 in. (114 mm)3.5 in. (89 mm)3.3 in. (85 mm)3.1 in. (79 mm)

RDSS-CLIP: Sealing Between Cables

When a duct holds three or more cables, an RDSS-CLIP (a sealing star) goes between the cables to close the gaps. TE describes the clip's high-temperature sealant as filling all the spaces between the cables, and lists it for medium voltage cable including unjacketed concentric neutral.

Cables in the ductClips needed
1 to 2None (except where the chart is marked *)
3 to 41 clip
5 to 72 clips
More than 7Contact TE

One clip seals up to four cables, and each additional three cables need one more clip. Each kit has a matching clip.

Clips come 5 per box and are ordered separately from the seal elements. The clip sealant, S-1278, is sold separately.

Installing and Removing an RDSS Seal

TE says the whole installation takes only a few minutes, even in tight spaces, with no mixing or filling of liquids.

StepWhat to do
1Apply the lubricant to the sealant strips of the RDSS bladder, or to the clip if you use one. TE's lubricant is a soap solution applied with a sponge head.
2For three or more cables, position the clip between the cables
3Wrap the seal around the cable and push it into the duct
4Inflate the bladder with the hand inflator to 3 bar. The gauge and pressure limiter keep it at 3.0 +/- 0.2 bar.
5Remove the filling tube. The gel valve closes automatically so the bladder keeps its pressure.

TE says a seal can be removed by releasing the gas, without damaging the ducts, so cables can be replaced or added later and the duct sealed again. Because the seal adapts itself to the duct, it also seals deformed ducts, and it can be installed in a duct that still has water flowing through it. See the installation instructions (EPP-0570) for the full procedure.

Inflation Tools and Accessories

Part numberWhat it isPackage
RDSS-IT-16Inflation tool with on/off switch, gauge and automatic pressure limiting, uses CO2 cylinders. Supplied in a carrying case with instructions.1 per box
E7512-016016 g CO2 cylinders for the RDSS-IT-16. TE's catalog says one cylinder is enough for about 5 RDSS-100 seals, and the cut sheet says about 4.10 per box
RDSS-IG-SR-ASInflation tool for customer-supplied nitrogen or compressed air, with gauge, auto shutoff and hose connections1 per box
E7512-0220, E7512-0240, E7512-0260Spare tube snap assembly, pressure gauge assembly and delivery pipe for the RDSS-IT-161 per box each
S-1278-3x61x7620RDSS sealant roll25 ft roll
RDSS-AT/AP-150Adapter for the RDSS-150 when the cable bundle is under 2.4 in. (60 mm)1 per box
RDSS-AD-210Adapter used with the RDSS-125 and RDSS-150. The cut sheet lists it for 6.5 to 8.0 in. (165 to 210 mm) ducts.4 per box
E4540-1250RDSS-LUBE installation lubricant25 per box

RDSS Kits We Carry

TE's catalog packs RDSS seal elements 10 to a carton with one bottle of lubricant and the installation instructions. The RDSS-100 is also sold in packs of 3. Duct sizes are from TE's catalog.

KitDuct inside diameterPack
RDSS-45 (S10)32.5 to 45 mm (about 1.28 to 1.77 in.)10 wraps
RDSS-60 (S10)45 to 60 mm (about 1.77 to 2.36 in.)10 wraps
RDSS-75 (S10)55 to 75 mm (about 2.17 to 2.95 in.)10 wraps
RDSS-100 (S10)75 to 120 mm (about 2.95 to 4.72 in.)10 wraps
RDSS-100 (S3)75 to 120 mm (about 2.95 to 4.72 in.)3 wraps, 1 lubricant dispenser, installation instructions; sold in multiples of 3
RDSS-125 (S10)100 to 150 mm (about 3.94 to 5.91 in.)10 wraps
RDSS-150 (S10)125 to 180 mm (about 4.92 to 7.09 in.), cable only10 wraps

RDSS vs. Foam Duct Sealant

RDSS is a mechanical seal and the Polywater foams are chemical seals, so they suit different jobs. See the ZipSeal vs FST vs AFT guide for the foam side.

Raychem RDSSPolywater foam (ZipSeal, FST, AFT)
How it sealsInflated bladder presses sealant strips against the duct and cablesTwo-part urethane foam expands and hardens into a closed-cell seal
Tested water head0.3 bar (3 m, about 10 ft) per TE's catalogZipSeal 30 ft, FST 22 ft continuous, AFT 11 ft on PVC
SizingA kit per duct size, within a maximum cable diameterFST for 2 to 8 in. conduits, AFT for 3/4 to 10 in., ZipSeal for small conduits and innerducts
Several cables in a ductRDSS-CLIPs close the gaps between cablesFoam fills around the cables; separate them first
MixingNoneTwo-part foam mixes in the nozzle
ToolsHand inflator, with CO2 cylinders or nitrogen or compressed airDispensing tool or aerosol can
RemovalRelease the gas and the seal comes out without damaging the ductPierce and break the foam bond, then pull the plug
ConditionsDry or wet installation, in concrete, plastic or steel ductsFoam does not cure below 40 degrees F (4 degrees C) per Polywater's FAQ

Frequently Asked Questions About the Raychem RDSS

What is the RDSS?

Raychem's Rayflate Duct Sealing System, an inflatable bladder with sealant strips that seals around cables in a duct.

How is it inflated?

To 3.0 +/- 0.2 bar (about 45 psi), with the RDSS-IT-16 tool and CO2 cylinders or the RDSS-IG-SR-AS tool and nitrogen or compressed air.

Can it be installed in a wet duct?

Yes. TE lists installation in dry or wet conditions, and says the seal works even with water flowing through the duct.

What ducts does it work in?

Concrete, plastic or steel. TE says it does not depend on duct ovality, so it also seals deformed ducts.

What pressure does it hold?

TE tested water and gas tightness at up to 0.3 bar, with the cables under vibration, bending, torsion, pull and push.

How long does it last?

TE's calculations show the seals still hold 0.3 bar of a 3 m water column after 30 years.

How do I seal a duct with several cables?

Use RDSS-CLIPs between the cables. One clip seals up to four cables, with one more clip for every three additional cables. For more than seven cables, contact TE.

What if the cable bundle is too big?

Do not exceed the maximum cable bundle diameter for the duct, or the bladder may not inflate properly. Subtract 5 mm from the chart value for each clip used, and move up to the next kit or ask TE if the bundle is too large.

Can I remove the seal and reuse the duct?

Yes. Release the gas and the seal comes out without damaging the duct, so cables can be changed and the duct sealed again.

How many seals does a CO2 cylinder inflate?

TE's catalog says about 5 RDSS-100 seals per 16 g cylinder, and the cut sheet says about 4.

Can it seal ducts larger than 6 in.?

Yes. The RDSS-150 covers ducts up to 180 mm (about 7.1 in.), and TE pairs the RDSS-AD-210 adapter with the RDSS-125 and RDSS-150. For larger ducts, ask TE.