Richards deadbreak cable adapters are lettered, and the letter you need depends on one number: the diameter over the cable insulation. Pick the wrong letter and the adapter will not seat correctly on the cable. This guide has the Richards sizing tables for 15/25 kV and 35 kV, shows which Richards products use them, and covers the matching jacket seal kits. All values come from the Richards Medium Voltage Products catalog (Tables W1 and W3).
The cable adapter fits over the prepared cable insulation and matches it to the deadbreak elbow or disconnectable joint. In Richards part numbers it is the "W" field. The adapter part number is P625CA-W for 15/25 kV and P635CA-W for 35 kV, where W is the size letter from the tables below.
The same sizing tables are used across Richards' 600/900 A deadbreak elbows, joints and splices, including the 62LCT, P625JS and P625JI/JY/JH/JU/JL/JE families at 15/25 kV and the matching 63 and P635 families at 35 kV. See our guides to the deadbreak elbow and the JSCS sleeve.
Some ranges overlap, so a cable can fall in two sizes. If yours does, send us the cable details and we will confirm with Richards.
| Size (W) | Min Insulation Diameter | Max Insulation Diameter | Store Part |
|---|---|---|---|
| E | 0.530 in (13.5 mm) | 0.675 in (17.2 mm) | P625CA-E |
| F | 0.640 in (16.3 mm) | 0.820 in (20.8 mm) | P625CA-F |
| G | 0.760 in (19.3 mm) | 0.950 in (24.1 mm) | P625CA-G |
| H | 0.850 in (21.6 mm) | 1.050 in (26.7 mm) | P625CA-H |
| J | 0.980 in (24.9 mm) | 1.180 in (30.0 mm) | P625CA-J |
| K | 1.090 in (27.7 mm) | 1.310 in (33.2 mm) | P625CA-K |
| L | 1.180 in (30.0 mm) | 1.465 in (37.2 mm) | P625CA-L |
| LM | 1.280 in (32.5 mm) | 1.430 in (36.3 mm) | P625CA-LM |
| M | 1.370 in (34.8 mm) | 1.630 in (41.4 mm) | P625CA-M |
| MN | 1.480 in (37.6 mm) | 1.700 in (43.2 mm) | P625CA-MN |
| N | 1.515 in (38.5 mm) | 1.780 in (45.2 mm) | P625CA-N |
| PA | 1.665 in (42.3 mm) | 1.785 in (45.3 mm) | P625CA-PA |
| P | 1.725 in (43.8 mm) | 1.935 in (49.2 mm) | P625CA-P |
| PQ | 1.795 in (45.6 mm) | 1.935 in (49.2 mm) | P625CA-PQ |
| Size (W) | Min Insulation Diameter | Max Insulation Diameter | Store Part |
|---|---|---|---|
| H | 0.850 in (21.6 mm) | 1.050 in (26.7 mm) | P635CA-H |
| J | 0.980 in (24.9 mm) | 1.180 in (30.0 mm) | P635CA-J |
| K | 1.090 in (27.7 mm) | 1.310 in (33.3 mm) | P635CA-K |
| L | 1.180 in (30.0 mm) | 1.465 in (37.2 mm) | P635CA-L |
| LM | 1.280 in (32.5 mm) | 1.430 in (36.3 mm) | P635CA-LM |
| M | 1.370 in (34.8 mm) | 1.630 in (41.4 mm) | P635CA-M |
| MN | 1.480 in (37.6 mm) | 1.700 in (43.2 mm) | P635CA-MN |
| N | 1.515 in (38.5 mm) | 1.780 in (45.2 mm) | P635CA-N |
| P | 1.725 in (43.8 mm) | 1.935 in (49.2 mm) | P635CA-P |
| Q | 1.900 in (48.3 mm) | 2.120 in (53.9 mm) | P635CA-Q |
| R | 2.000 in (50.8 mm) | 2.235 in (56.8 mm) | P635CA-R |
Richards notes that copper-top and 900 A copper versions of these kits are not listed but use the same sizing (change the 6 to a 7 or 9), and that versions without a test point also use the same sizing. The store listings for 15/25 kV adapters that are not linked above are available on request.
200 A loadbreak elbows use a different table (Table W2), with sizes A through D for the 21LBT family.
The jacket seal is sized to the cable adapter letter. Richards lists these common options, with the kit suffix used in a full part number:
| Suffix | Part Number | What It Is | For Cable Adapter Size | Seal Diameter Range |
|---|---|---|---|---|
| AC | PCRK-005-1 | Cold shrink seal | E to J | 0.95 to 1.94 in |
| AD | PCRK-005-2 | Cold shrink seal | K to P | 1.28 to 2.67 in |
| AG | PCRK-005-3 | Cold shrink seal | Larger than P | 1.60 to 3.50 in |
| BC | PCRK16-2 | Cold shrink seal and #6 AWG tinned copper braid with constant force spring | E to J | 0.95 to 1.94 in |
| DD | PCRK12-3 | Cold shrink seal and #4 AWG tinned copper braid with constant force spring | K to P | 1.28 to 2.67 in |
| DG | PCRK12-6 | Cold shrink seal and #4 AWG tinned copper braid with constant force spring | Larger than P | 1.60 to 3.50 in |
The braid is supplied at 36 inches. Contact the factory if you need a different length.
The cable adapter letter (W) handles the insulation diameter. The lug code (X) handles the conductor. Both go in the elbow or joint part number, as in 6-2-LC-N-2-LM-23-D-D, where LM is the adapter and 23 is the lug code. For the lug code tables, see our JSCS guide and deadbreak elbow guide.
Measure or look up the diameter over the cable insulation, then find it in Table W1 (15/25 kV) or Table W3 (35 kV). The letter in the last column is your size.
P625CA is for 15/25 kV systems and P635CA is for 35 kV systems.
Richards' 35 kV table starts at size H (0.850 in minimum) and runs through R. The 15/25 kV table starts smaller, at size E.
Yes. Richards uses the same W table for the 62LCT elbows, the P625JS/JSCS sleeves and the P625 joint families at 15/25 kV, and the matching 35 kV families use Table W3.
Match it to the adapter letter. PCRK-005-1 is for E to J, PCRK-005-2 for K to P, and PCRK-005-3 for sizes larger than P. The PCRK16-2, PCRK12-3 and PCRK12-6 versions add a tinned copper braid for shield grounding.
Some ranges overlap. Contact Powertech Associates with the cable details and we will confirm the right size with Richards.