Squirrels and other animals can bridge a substation bus insulator and cause an outage. The TE Raychem BISG is a guard that fits over an installed insulator to stop that. TE's catalog calls it the Bus Isolation Squirrel Guard, and its test report and our store call it the bus insulator guard. This guide lists the BISG, BISG-24 and BISG 100/400 sizes, colors and installation methods. Specs are from TE's Raychem Wildlife & Asset Protection catalog (2019). See also the TE Raychem Wildlife and Asset Protection overview.
Dimensions are in inches, with mm in parentheses. The overall product diameter is in inches as printed in the catalog.
| Catalog number | Insulator core diameter range | Overall product diameter (in) | Color | Installation |
|---|---|---|---|---|
| BISG-60/115-02 (S10) | 2.4 to 4.5 (60 to 115) | 24 | Red | De-energized |
| BISG-60/115-03-HOT (B10) | 2.4 to 4.5 (60 to 115) | 24 | Red | Two stick (energized) |
| BISG-G-60/115-02 (S10) | 2.4 to 4.5 (60 to 115) | 24 | Gray | De-energized |
| BISG-G-60/115-03-HOT-B10 | 2.4 to 4.5 (60 to 115) | 24 | Gray | Two stick (energized) |
| BISG-24-01 (B10) | 2.5 to 5.0 (62 to 125) | 24 | Red | One stick (energized) |
| BISG-G-24-01 (B10) | 2.5 to 5.0 (62 to 125) | 24 | Gray | One stick (energized) |
| BISG-100/400 (B3) | 1.50 to 4.50 (38 to 115) | 16 | Red | De-energized |
| BISG-G-100/400 (B3) | 1.50 to 4.50 (38 to 115) | 16 | Gray | De-energized |
One BISG installs on one insulator. The standard package is 10 BISG-60/115-02 or 10 BISG-24-01 assemblies per box.
For the BISG-24 power arc and wind tunnel test data, see our TE Raychem Wildlife and Asset Protection overview.
| Feature | TE statement |
|---|---|
| Materials | High voltage outdoor materials. The polymer is rugged, track resistant and UV stable, for long-term performance in any environment. |
| Colors | Red or gray |
| Sizes | Two to five inches from the factory, with a grill design that allows easy field modifications |
| Visibility | Allows excellent visibility of switch blades and other components |
| Arc and wind | Provides resistance to power arcs and high winds |
| Installation | Designed so one person can install it quickly with hot sticks on vertical or horizontal mounted insulators |
| Track record | TE says the guard has reliably prevented animal-caused outages in electrical substation equipment for years |
| Test reports | EDR-5310 and EDR-5517 (Bus Insulator Squirrel Guard, BISG-24-01) |
| Method | Models in the catalog |
|---|---|
| De-energized | BISG-60/115-02, BISG-G-60/115-02, BISG-100/400, BISG-G-100/400 |
| Two stick, energized | BISG-60/115-03-HOT, BISG-G-60/115-03-HOT |
| One stick, energized | BISG-24-01, BISG-G-24-01 |
Follow your own work rules and TE's installation instructions for any energized installation.
| Step | What to do |
|---|---|
| 1. Measure the insulator core | Measure the insulator core diameter in inches. |
| 2. Match the range | Pick the model whose core range includes it: 60/115 (2.4 to 4.5 in), 24 (2.5 to 5.0 in) or 100/400 (1.50 to 4.50 in). |
| 3. Pick the install method | De-energized, one stick or two stick, based on how your crew will work. |
| 4. Pick the color | Red or gray. The catalog lists both colors for every size. |
| 5. Count insulators | One BISG per insulator. Order by the box. |
It covers an installed substation bus insulator so animals cannot bridge it, while still letting crews see switch blades and other components.
TE lists energized models: the BISG-24-01 installs with one stick, and the BISG-60/115-03-HOT installs with two sticks. The other models are listed for de-energized installation.
One. A single BISG installs on one insulator.
TE says the grill design allows easy field modifications, and that sizes range from two to five inches from the factory.
The catalog lists both colors for each size and does not state a performance difference.
EDR-5310, and EDR-5517 for the BISG-24-01.
Powertech Associates supplies TE Raychem wildlife and asset protection products. Order online: BISG-G-60/115-02, BISG-G-24-01 or BISG-G-100/400. For red versions or help matching a guard to your insulator, contact Powertech Associates at info@powertech-upsc.com or (860) 678-8772.
Last updated: November 2026.