A cold shrink termination is a pre-stretched silicone body that you slide over the cable end and let collapse into place, with no torch. TE Connectivity's Raychem CST line covers 5 to 35 kV polymeric cable in two versions: the CSTI for indoor use and the CSTO for outdoor use. This guide covers what each one does, how the part numbers break down, which lugs go with it, and how to pick the right size.
The CST is a cold applied termination for extruded cable, such as XLPE or EPR insulated cable. It connects the cable to a transformer, switchgear, an overhead line or a busbar. The body is liquid silicone rubber, supplied pre-expanded on a spiral holdout. You position it, pull out the holdout, and it shrinks onto the cable.
TE lists these features for the line:
TE's CST cut sheet lists the line as Class 1A and in compliance with IEEE-48 and CENELEC HD 629.1.S2, which TE says includes IEC, BS, VDE and other international specifications. TE lists an operating temperature range of -40 to 40 degrees C for the line and a 3 year shelf life.
The I and O stand for indoor and outdoor.
| CSTI (indoor) | CSTO (outdoor) | |
|---|---|---|
| Where it goes | Switchgear, enclosures and other protected spaces | Open air, such as pole, pad or substation terminations |
| Body | Indoor body | Outdoor body with more sheds to increase creepage distance |
| Sheds (TE catalog) | 3 on the 5/8 to 28 kV kits, 7 on the 35 kV kits | 4 on the 5/8 to 28 kV kits, 8 on the 35 kV kits |
| Installed length (TE data) | 380 mm | 380 mm |
TE's online product page lists 4 sheds on the CSTI-152G and CSTI-153G, so confirm the count with us or TE if it matters for your spec. Both use the same pre-expanded holdout approach and the same stress control design. If the termination will see rain, pollution or direct sun, choose the CSTO.
TE's ordering guide builds the number from codes in order. Take CSTO-153G as an example.
TE's ordering guide also has an L code for a long neck body, and a -3 code for 3/C cable. Without them the kit is a standard 1/C termination. A connector code at the end adds a lug or pin to the kit, covered next.
Add a connector code to the end of the part number and the kit ships with that lug or pin. CSTO-283G-CL4, for example, is the CSTO-283G with a 3/0 copper compression lug. Leave the code off and no connector is included. This table is from TE's CST ordering guide (EPP-2629, 8/18).
| Code | Type | Use range (in) | Conductor size |
|---|---|---|---|
| (blank) | No connector included | ||
| -CP0 | Compression pin (12 inches) | #2 | |
| -CP1 | Compression pin (12 inches) | #1 | |
| -CP2 | Compression pin (12 inches) | 1/0 | |
| -CP3 | Compression pin (12 inches) | 2/0 | |
| -CP4 | Compression pin (12 inches) | 3/0 | |
| -CP5 | Compression pin (12 inches) | 4/0 | |
| -CL0 | Copper compression lug | #2 | |
| -CL1 | Copper compression lug | #1 | |
| -CL2 | Copper compression lug | 1/0 | |
| -CL3 | Copper compression lug | 2/0 | |
| -CL4 | Copper compression lug | 3/0 | |
| -CL5 | Copper compression lug | 4/0 | |
| -CL6 | Copper compression lug | 350 | |
| -CL7 | Copper compression lug | 500 | |
| -CL8 | Copper compression lug | 750 | |
| -CL9 | Copper compression lug | 1000 | |
| -SP0 | ShearBolt pin | .258 to .373 | #2 to 1/0 |
| -SP1 | ShearBolt pin | .376 to .528 | 2/0 to 4/0 |
| -SL0 | ShearBolt lug | .268 to .528 | #2 to 4/0 |
| -SL1 | ShearBolt lug | .268 to .681 | #2 to 350 |
| -SL2 | ShearBolt lug | .616 to .998 | 350 to 750 * |
| -SL3 | ShearBolt lug | .813 to 1.152 | 600 to 1000 * |
| -SL4 | ShearBolt lug | 1.19 to 1.25 | 1250 * |
* TE's catalog says the -SL2 and -SL3 lugs must be used with a long neck CST, except on 35 kV part numbers, and to contact TE Technical Support about long neck body requirements for the -SL4 lug. TE also notes that its aluminum connectors are tin plated and can be used on copper or aluminum conductors. Compression sizes are matched to one conductor size each, while the ShearBolt lugs take a range, so a single ShearBolt code can often cover more than one cable.
From TE's data for the US versions, including TE's CST data sheet and the CSTI instruction sheet (PII-70304). Conductor size is in AWG or kcmil and insulation diameter is in millimeters. Part numbers without a link are TE catalog items we can order on request.
| Catalog # | Voltage | Shield | Conductor (AWG/kcmil) | Insulation OD (mm) |
|---|---|---|---|---|
| CSTO-152G | 15 kV | Tape | #2 to 250 | 16.5 to 27 |
| CSTO-152J | 15 kV | JCN | #2 to 250 | 16.5 to 27 |
| CSTO-153G | 15 kV | Tape | 350 to 500 | 24.5 to 34.5 |
| CSTO-153J | 15 kV | JCN | 350 to 500 | 24.5 to 34.5 |
| CSTO-154G | 15 kV | Tape | 600 to 1250 | 32.5 to 52 |
| CSTO-154J | 15 kV | JCN | 600 to 1250 | 32.5 to 52 |
| CSTO-282G | 28 kV | Tape | 1 to 2/0 | 16.5 to 27 |
| CSTO-282J | 28 kV | JCN | 1 to 2/0 | 16.5 to 27 |
| CSTO-283G | 28 kV | Tape | 2/0 to 350 | 24.5 to 34.5 |
| CSTO-283J | 28 kV | JCN | 2/0 to 350 | 24.5 to 34.5 |
| CSTO-284G | 28 kV | Tape | 500 to 1250 | 32.5 to 52 |
| CSTO-284J | 28 kV | JCN | 500 to 1250 | 32.5 to 52 |
| CSTO-352G | 35 kV | Tape | 1/0 to 350 | 24.3 to 36 |
| CSTO-352J | 35 kV | JCN | 1/0 to 350 | 24.3 to 36 |
| CSTO-353G | 35 kV | Tape | 250 to 750 | 32.4 to 48 |
| CSTO-354G | 35 kV | Tape | 750 to 2000 | 43.2 to 64 |
| Catalog # | Voltage | Shield | Conductor (AWG/kcmil) | Insulation OD (mm) |
|---|---|---|---|---|
| CSTI-82G | 5/8 kV | Tape | 2/0 to 350 | 16.5 to 27 |
| CSTI-83G | 5/8 kV | Tape | 500 to 750 | 24.5 to 34.5 |
| CSTI-84G | 5/8 kV | Tape | 1000 | 32.5 to 52 |
| CSTI-152G | 15 kV | Tape | #2 to 250 | 16.5 to 27 |
| CSTI-152J | 15 kV | JCN | #2 to 250 | 16.5 to 27 |
| CSTI-153G | 15 kV | Tape | 350 to 500 | 24.5 to 34.5 |
| CSTI-153J | 15 kV | JCN | 350 to 500 | 24.5 to 34.5 |
| CSTI-154G | 15 kV | Tape | 600 to 1250 | 32.5 to 52 |
| CSTI-282G | 28 kV | Tape | 1 to 2/0 | 16.5 to 27 |
| CSTI-283G | 28 kV | Tape | 2/0 to 350 | 24.5 to 34.5 |
| CSTI-284G | 28 kV | Tape | 500 to 1250 | 32.5 to 52 |
| CSTI-352G | 35 kV | Tape | 1/0 to 350 | 24.3 to 36 |
| CSTI-353G | 35 kV | Tape | 250 to 750 | 32.4 to 48 |
| CSTI-354G | 35 kV | Tape | 750 to 2000 | 43.2 to 64 |
The 28 kV rows follow TE's catalog, which lists the 282 size as #1 to 2/0 for both the CSTI and the CSTO. For JCN cable, add a J to the end of the number, for example CSTI-152 becomes CSTI-152J. For other shielded cable, add a G.
TE's catalog lists long neck bodies for the largest size in each class, with an L after the CSTI or CSTO. TE also lists a 5/8 kV long neck kit for 1000 kcmil. Insulation OD is 32.5 to 52 mm on all of them.
| Catalog # | Voltage | Conductor (AWG/kcmil) | Insulation OD (mm) |
|---|---|---|---|
| CSTIL-154 | 15 kV | 600 to 1250 | 32.5 to 52 |
| CSTOL-154 | 15 kV | 600 to 1250 | 32.5 to 52 |
| CSTIL-284 | 28 kV | 500 to 1250 | 32.5 to 52 |
| CSTOL-284 | 28 kV | 500 to 1250 | 32.5 to 52 |
TE's installation video walks through a full CSTI or CSTO install for IEEE standard cable. The steps are the same idea every time: prep the cable and the shield, install the lug, slide the termination into position, and pull out the spiral holdout to let it shrink down. Always follow TE's instruction sheet in the kit for the exact dimensions.
Learn how to install our Raychem Cold Shrink Terminations CST for indoor and outdoor use up to 35 kV for IEEE standard networks.
Both work. Cold shrink is the faster install, needs no torch and fits tight spaces, which is why it is common in switchgear compartments and on live-front pad-mounted gear. Heat shrink has a longer track record and shrinks to fit out-of-round cable. TE makes both, and we compare them in our Raychem splice guide. For splicing instead of terminating, see our CSJA cold shrink joint write-up. If you go with heat shrink, you will need a torch. See our Raychem torches and accessories guide.
Cold Shrink Termination. The CSTI is the indoor version and the CSTO is the outdoor version.
The US versions we stock cover 5/8, 15, 28 and 35 kV classes. TE lists the line for polymeric cable up to 35 kV.
TE's CST cut sheet lists compliance with IEEE-48 and CENELEC HD 629.1.S2, which includes IEC, BS, VDE and other international specifications.
No. It is pre-expanded on a spiral holdout. You pull the holdout out and the silicone body shrinks onto the cable.
G is for cable with a copper tape shield. J is for JCN cable, which has a jacketed concentric neutral. Insulation and conductor ranges are the same for a given size.
No. The CSTI is the indoor version. TE says the outdoor version includes sheds to increase creepage distance, and the CSTO has more of them than the CSTI. Use the CSTO outdoors.
TE lists a shelf life of 3 years.
Only if the part number ends in a connector code. TE offers compression pins (CP), copper compression lugs (CL), ShearBolt pins (SP) and ShearBolt lugs (SL). With no code, no connector is included.
CL is a copper compression lug, CP is a 12 inch compression pin, SL is a ShearBolt lug and SP is a ShearBolt pin. The number after the letters sets the conductor size or range, as listed in the lug table.
Powertech Associates and Utility Power Supply Company represent TE Connectivity across New England and New York State. Tell us the voltage, cable type and conductor size and we will help you pick the kit. Contact us at info@powertech-upsc.com or (860) 678-8772.
Last updated: November 2026.