A cold shrink termination is a pre-stretched silicone body that you slide over the cable end and let collapse into place, with no torch. TE Connectivity's Raychem CST line covers 15 to 35 kV polymeric cable in two versions: the CSTI for indoor use and the CSTO for outdoor use. This guide covers what each one does, how the part numbers break down, and how to pick the right size.
The CST is a cold applied termination for extruded cable, such as XLPE or EPR insulated cable. It connects the cable to a transformer, switchgear, an overhead line or a busbar. The body is liquid silicone rubber, supplied pre-expanded on a spiral holdout. You position it, pull out the holdout, and it shrinks onto the cable.
TE lists these features for the line:
The CST is qualified to IEEE 404 for the US versions, and TE publishes a separate CENELEC HD 629.1 version for IEC networks. TE lists an operating temperature range of -40 to 40 degrees C for the line and a 3 year shelf life.
The I and O stand for indoor and outdoor.
| CSTI (indoor) | CSTO (outdoor) | |
|---|---|---|
| Where it goes | Switchgear, enclosures and other protected spaces | Open air, such as pole, pad or substation terminations |
| Body | Standard termination body | Adds sheds to increase creepage distance |
| Sheds (TE data) | None listed on the US kits | 4 sheds on the US kits |
| Installed length (TE data) | 380 mm | 380 mm |
Both use the same pre-expanded holdout approach and the same stress control design. If the termination will see rain, pollution or direct sun, choose the CSTO.
Take CSTO-153G as an example.
Part numbers followed by a CL or CP suffix, such as CSTO-283G-CL4, are the same termination sold with a specific conductor size in mind. Contact us if you need one.
From TE's data for the US versions. Conductor size is in AWG or kcmil and insulation diameter is in millimeters. Each CSTO size comes in a tape (G) and a JCN (J) version, and the sizes are the same for both. Part numbers without a link are TE catalog items we can order on request.
| Catalog # | Voltage | Shield | Conductor (AWG/kcmil) | Insulation OD (mm) |
|---|---|---|---|---|
| CSTO-152G | 15 kV | Tape | #2 to 250 | 16.5 to 27 |
| CSTO-152J | 15 kV | JCN | #2 to 250 | 16.5 to 27 |
| CSTO-153G | 15 kV | Tape | 350 to 500 | 24.5 to 34.5 |
| CSTO-153J | 15 kV | JCN | 350 to 500 | 24.5 to 34.5 |
| CSTO-154G | 15 kV | Tape | 600 to 1250 | 32.5 to 52 |
| CSTO-154J | 15 kV | JCN | 600 to 1250 | 32.5 to 52 |
| CSTO-282G | 28 kV | Tape | 1 to 3/0 | 16.5 to 27 |
| CSTO-282J | 28 kV | JCN | 1 to 3/0 | 16.5 to 27 |
| CSTO-283G | 28 kV | Tape | 2/0 to 350 | 24.5 to 34.5 |
| CSTO-283J | 28 kV | JCN | 2/0 to 350 | 24.5 to 34.5 |
| CSTO-284G | 28 kV | Tape | 500 to 1250 | 32.5 to 52 |
| CSTO-284J | 28 kV | JCN | 500 to 1250 | 32.5 to 52 |
| Catalog # | Voltage | Shield | Conductor (AWG/kcmil) | Insulation OD (mm) |
|---|---|---|---|---|
| CSTI-152G | 15 kV | Tape | #2 to 250 | 16.5 to 27 |
| CSTI-153G | 15 kV | Tape | 350 to 500 | 24.5 to 34.5 |
We also stock these CST kits, including the 35 kV class. TE does not list sizes for them on its public CST page, so contact us and we will confirm the conductor and insulation range before you order.
TE's installation video walks through a full CSTI or CSTO install for IEEE standard cable. The steps are the same idea every time: prep the cable and the shield, install the lug, slide the termination into position, and pull out the spiral holdout to let it shrink down. Always follow TE's instruction sheet in the kit for the exact dimensions.
Learn how to install our Raychem Cold Shrink Terminations CST for indoor and outdoor use up to 35 kV for IEEE standard networks.
Both work. Cold shrink is the faster install, needs no torch and fits tight spaces, which is why it is common in switchgear compartments and on live-front pad-mounted gear. Heat shrink has a longer track record and shrinks to fit out-of-round cable. TE makes both, and we compare them in our Raychem splice guide. For splicing instead of terminating, see our CSJA cold shrink joint write-up.
Cold Shrink Termination. The CSTI is the indoor version and the CSTO is the outdoor version.
The US versions we stock cover 15, 28 and 35 kV classes. TE lists the line as qualified to IEEE 404 up to 35 kV.
No. It is pre-expanded on a spiral holdout. You pull the holdout out and the silicone body shrinks onto the cable.
G is for cable with a copper tape shield. J is for JCN cable, which has a jacketed concentric neutral. Insulation and conductor ranges are the same for a given size.
No. The CSTI has no sheds and is meant for indoor use. Use the CSTO outdoors.
TE lists a shelf life of 3 years.
Range-taking mechanical lugs are available for the CST line. Contact us to match one to your conductor.