Raychem HVT and HVT-Z Terminations: Sizes, Differences and How to Choose

December 15, 2024

Raychem HVT and HVT-Z Terminations: Sizes, Differences and How to Choose

A termination has to control electrical stress at the end of the cable shield and keep out moisture and pollution for the life of the cable. TE Connectivity's Raychem HVT and HVT-Z are heat shrink terminations for medium voltage shielded cable from 5 to 35 kV. They look similar on a catalog page, but they are built differently. This guide covers what each one is, how they differ, how to size them, and how to read the part number.

What is the Raychem HVT termination?

The HVT is a termination system with a non-tracking, insulating outer surface designed for long-term electrical stress and surface pollution. TE rates it for severely polluted areas and all installation conditions, including top-feed installation. It is fully qualified per IEEE 48 as a Class I termination.

TE lists these features:

  • Standard indoor and outdoor kits for all plastic cable types, including armored cable
  • One installation technique for all cable types, including armored cable, so no retraining is needed
  • Can be installed upright or inverted
  • Can bend to the same radius as the cable
  • No special adapters or accessories needed
  • Non-tracking material that is maintenance free and needs no periodic cleaning
  • Load-cycle testing confirms thermomechanical compatibility with the cable

What is the Raychem HVT-Z termination?

The HVT-Z is a co-extruded, one-piece termination for shielded cable. Its main component is Raychem's established non-tracking tube with a co-extruded stress-control grading layer. That layer uses zinc oxide (ZnO) ceramic semiconductor technology, which TE says gives better discharge and impulse performance. When the termination is shrunk, the coating softens and conforms to irregular surfaces, providing moisture sealing and electrical stress control.

The HVT-Z is also fully qualified per IEEE 48 as a Class I termination. It can be ordered with TE's aluminum ShearBolt terminals, which are range-taking mechanical connectors for #2 compact through 1000 kcmil stranded Class B conductors.

HVT vs HVT-Z: what is the difference?

HVTHVT-Z
ConstructionNon-tracking insulating termination systemCo-extruded one-piece termination with a ZnO stress-control grading layer
Voltage classes5/8, 15, 25 and 35 kV5/8, 15, 25 and 35 kV
Indoor and outdoor kits-G indoor, -SG outdoor-G indoor, -SG outdoor
Installed length10.5 in (5/8 kV), 15.0 in (15 kV), 28.0 in (25 kV), 33.0 in (35 kV)11.5 in (5/8 and 15 kV), 19.0 in (25 and 35 kV)
ShearBolt terminal kitsNot listed on the spec sheetAvailable (-T5, -T8 and -T9 kits)
StandardIEEE 48, Class IIEEE 48, Class I

Installed lengths above are as printed on TE's sheets. The HVT has a wider size range at 25 and 35 kV, with a size 5 kit for 2000 to 2500 kcmil cable. If your cable falls in a range that only one of them covers, that decides it.

HVT test ratings

From TE's HVT specification sheet. Continuous current is equal to the cable ampacity for every class.

TestHVT-80 (5-8 kV)HVT-150 (15 kV)HVT-250 (25 kV)HVT-350 (35 kV)
AC withstand, 1 minute (kV)35506590
DC withstand, 15 minutes (kV)6575105140
Partial discharge, minimum kV (3 pC or less)915.625.836
Impulse withstand 1.2 x 50 us, outdoor (crest kV)95110150200
Impulse withstand 1.2 x 50 us, indoor (crest kV)8095125150
Wet withstand, 10 seconds (kV rms)30456080
Dry withstand, 6 hours (kV rms)25355575

The HVT-250 series meets the requirements for 25/28 kV systems. Outdoor kits were tested with skirts (rain sheds), and indoor kits have no skirts.

How do you read an HVT or HVT-Z part number?

The number follows one pattern on both products. Take the HVT-Z-153-SG as an example.

  • HVT or HVT-Z: the product
  • The first digits (8, 15, 25 or 35): the voltage class. 8 is the 5/8 kV class, 15 is 15 kV, 25 is 25 kV and 35 is 35 kV
  • The last digit (0 to 5): the size, which steps up with the cable size, from the smallest conductor range to the largest
  • -G or -SG: -G is the indoor kit with no skirts, and -SG is the outdoor kit with skirts
  • -T5, -T8 or -T9 (HVT-Z only): the kit includes a ShearBolt terminal

So the HVT-Z-153-SG is the HVT-Z for 15 kV, size 3 (400 to 1000 kcmil), outdoor version. The HVT-Z-252/352 and 253/353 kits share a size number because the same kit serves 25 and 35 kV cable of the same diameter.

HVT sizing tables

From TE's HVT specification sheet (document 1308239). Each size comes as an indoor -G kit and an outdoor -SG kit. Insulation diameter and jacket OD are in inches, with millimeters in parentheses. Kit numbers that link to a product page are in our online store.

HVT 5/8 kV

Indoor / Outdoor Kit5 kV Conductor8 kV ConductorInsulation DiameterJacket OD (max)
HVT-80-G / HVT-80-SG#4-#1 AWG#6-#2 AWG0.35-0.60 (9-15)0.95 (24)
HVT-81-G / HVT-81-SG1/0 AWG-250 kcmil#1-4/0 AWG0.60-0.95 (15-24)1.20 (30)
HVT-82-G / HVT-82-SG300-500 kcmil250-500 kcmil0.80-1.25 (20-32)1.50 (38)
HVT-83-G / HVT-83-SG600-1750 kcmil600-1750 kcmil1.10-1.75 (28-44)2.10 (53)
HVT-84-G / HVT-84-SG1500-2500 kcmil2000-2500 kcmil1.60-2.45 (41-62)2.75 (70)

HVT 15 kV

Indoor / Outdoor KitConductor SizeInsulation DiameterJacket OD (max)
HVT-151-G / HVT-151-SG#4 AWG-1/0 AWG0.60-0.95 (15-24)1.20 (30)
HVT-152-G / HVT-152-SG2/0 AWG-350 kcmil0.80-1.25 (20-32)1.50 (38)
HVT-153-G / HVT-153-SG400-1000 kcmil1.10-1.65 (28-42)2.10 (53)
HVT-154-G / HVT-154-SG1250-2500 kcmil1.60-2.45 (41-62)2.75 (70)

HVT 25 kV

Indoor / Outdoor KitConductor SizeInsulation DiameterJacket OD (max)
HVT-252-G / HVT-252-SG#2 AWG-250 kcmil0.80-1.25 (20-32)1.50 (38)
HVT-253-G / HVT-253-SG300-750 kcmil1.10-1.70 (28-43)2.10 (53)
HVT-254-G / HVT-254-SG1000-1750 kcmil1.60-2.45 (41-62)2.75 (70)
HVT-255-G / HVT-255-SG2000-2500 kcmil2.05-3.00 (52-76)3.45 (88)

HVT 35 kV

Indoor / Outdoor KitConductor SizeInsulation DiameterJacket OD (max)
HVT-352-G / HVT-352-SG#1 AWG-1/0 AWG0.80-1.25 (20-32)1.50 (38)
HVT-353-G / HVT-353-SG2/0 AWG-500 kcmil1.10-1.85 (28-47)2.10 (53)
HVT-354-G / HVT-354-SG750-1750 kcmil1.60-2.45 (41-62)2.75 (70)
HVT-355-G / HVT-355-SG2000-2500 kcmil2.05-3.00 (52-76)3.45 (88)

TE's HVT sheet also mentions URD, LC and HVT-M kit versions, with the URD and LC kits rated for 15 to 35 kV only and the HVT-M kits for 5/8 to 25 kV only. Ask us if your cable needs one of them.

HVT-Z sizing tables

From TE's HVT-Z data sheet (document E578). Each size comes as a -G indoor and -SG outdoor kit. The 5/8 kV kits have no skirts for outdoor operation, the 15 kV outdoor kits have 1 skirt, and the 25 and 35 kV outdoor kits have 4 skirts.

HVT-Z 5/8 kV

Indoor / Outdoor Kit5 kV Conductor8 kV ConductorInsulation DiameterJacket OD (max)
HVT-Z-80-G / SG#4-#1 AWG#6-#2 AWG0.35-0.60 (9-15)0.95 (24)
HVT-Z-81-G / SG1/0 AWG-250 kcmil#1-4/0 AWG0.60-0.95 (15-24)1.20 (30)
HVT-Z-82-G / SG300-500 kcmil250-500 kcmil0.80-1.25 (20-32)1.50 (38)
HVT-Z-83-G / SG600-1750 kcmil600-1750 kcmil1.10-1.75 (28-44)2.10 (53)
HVT-Z-84-G / SG1500-3500 kcmil1500-2500 kcmil1.60-2.45 (41-62)2.75 (70)

The installed length is 11.5 in (295 mm), and the kit can be cut shorter for use with MCK kits.

HVT-Z 15 kV

Indoor / Outdoor KitConductor Size
HVT-Z-151-G / HVT-Z-151-SG#4 AWG-1/0 AWG
HVT-Z-152-G / HVT-Z-152-SG2/0 AWG-350 kcmil
HVT-Z-153-G / HVT-Z-153-SG400-1000 kcmil
HVT-Z-154-G / HVT-Z-154-SG1250-2500 kcmil

The installed length is 11.5 in (295 mm), and the sheet lists 175 to 220 mil insulation thickness for the 15 kV class.

HVT-Z 25 and 35 kV

Indoor / Outdoor Kit25 kV Conductor35 kV ConductorInsulation DiameterJacket OD (max)
HVT-Z-252/352-G / SG#2 AWG-250 kcmil#1 AWG-1/0 AWG0.80-1.25 (20-32)1.50 (38)
HVT-Z-253/353-G / SG300-750 kcmil2/0 AWG-500 kcmil1.10-1.75 (28-44)2.10 (53)
HVT-Z-254/354-G / SG1000-2000 kcmil750-1750 kcmil1.60-2.45 (41-62)2.75 (70)

The installed length is 19.0 in (485 mm). The sheet lists 0.260 in insulation thickness for 25 kV and 0.345 in for 35 kV.

HVT-Z kits with ShearBolt terminals

These kits ship with an aluminum ShearBolt terminal. Pick the -G (indoor) or -SG (outdoor) kit, then add the terminal code (-T5, -T8 or -T9).

KitConductor RangeInsulation DiameterJacket OD (max)
5/8 kV (11.5 in installed length, no skirts for outdoor)
HVT-Z-81-G/SG-T55 kV: 1/0 AWG-250 kcmil; 8 kV: #1-4/0 AWG0.60-0.95 (15-24)1.20 (30)
HVT-Z-82-G/SG-T55 kV: 300-350 kcmil; 8 kV: 250-350 kcmil0.80-1.07 (20-27)1.50 (38)
HVT-Z-82-G/SG-T8350-500 kcmil0.85-1.25 (22-32)1.50 (38)
HVT-Z-83-G/SG-T9600-1000 kcmil1.10-1.40 (28-36)2.10 (53)
15 kV (11.5 in installed length, 1 skirt for outdoor)
HVT-Z-151-G/SG-T5#2 AWG-1/0 AWG0.65-0.95 (17-24)1.20 (30)
HVT-Z-152-G/SG-T52/0 AWG-350 kcmil0.80-1.25 (20-32)1.50 (38)
HVT-Z-153-G/SG-T8400-500 kcmil1.10-1.355 (28-34)2.10 (53)
HVT-Z-153-G/SG-T9600-1000 kcmil1.215-1.65 (32-42)2.10 (53)
25/35 kV (19.0 in installed length, 4 skirts for outdoor)
HVT-Z-252/352-G/SG-T525 kV: #2 AWG-250 kcmil; 35 kV: #1-1/0 AWG0.80-1.25 (20-32)1.50 (38)
HVT-Z-253/353-G/SG-T525 kV: 300-350 kcmil; 35 kV: 2/0 AWG-350 kcmil1.10-1.50 (28-38)2.0 (51)
HVT-Z-253/353-G/SG-T825 kV: 350-750 kcmil; 35 kV: 350-500 kcmil1.185-1.70 (30-43)2.10 (53)
HVT-Z-254/354-G/SG-T925 kV: 600-1000 kcmil; 35 kV: 600-1000 kcmil1.60-1.79 (41-45)2.75 (70)

HVT-Z-J and HVT-Z-SJ Kits for URD Cable

TE's catalog also lists HVT-Z kits with a -J ending for indoor and a -SJ ending for outdoor, with skirts. TE says both are suitable for unjacketed and jacketed URD cable. Sizes are based on 100% and 133% insulated cable to AEIC CS5 and CS6, with nominal insulation thickness of 175 mils at 15 kV (220 mils at 133%), 260 mils at 25 kV and 345 mils at 35 kV. Insulation diameter and jacket OD are in inches. Conductor ranges are as TE prints them. The 15 kV kits have an installed length of 11.5 in (300 mm) and the 25/35 kV kits 20 in (500 mm). Kits do not include connectors. TE lists test reports EDR-5322 (indoor, 15 kV), EDR-5323 (outdoor, 15 kV) and EDR-5338 (25 to 35 kV).

Indoor / Outdoor KitConductor SizeInsulation DiameterJacket OD (max)
15 kV
HVT-Z-151-J / HVT-Z-151-SJ#2-#1 AWG (one range printed)0.60-0.951.05
HVT-Z-152-J / HVT-Z-152-SJ100%: 2/0-250 kcmil; 133%: #2-4/0 AWG0.80-1.051.45
HVT-Z-153-J / HVT-Z-153-SJ100%: 350-500 kcmil; 133%: 250-500 kcmil1.05-1.401.9
HVT-Z-154-J / HVT-Z-154-SJ100%: 750-1000 kcmil; 133%: 750-1000 kcmil1.25-2.002.5
25/35 kV
HVT-Z-252/352-J / HVT-Z-252/352-SJ#1-3/0 AWG (one range printed)0.80-1.051.45
HVT-Z-253/353-J / HVT-Z-253/353-SJ25 kV: 4/0-500 kcmil; 35 kV: 1/0-4/0 AWG1.05-1.401.9
HVT-Z-254/354-J / HVT-Z-254/354-SJ25 kV: 750-1000 kcmil; 35 kV: 250-1000 kcmil1.25-2.002.5

HVT-50 Terminations for Non-Shielded 5 kV Cable

TE's catalog also lists the HVT-50 series, non-shielded polymeric heat shrink terminations for 5 kV cable. Sizes are based on 100% insulated cable to ICEA S-66-524, with nominal insulation thickness of 90 mils. The insulation diameter below is the minimum TE lists. Installed length is 12 in (300 mm). They come 3 single-conductor kits per box and do not include connectors.

KitConductor Size (AWG/kcmil)Insulation Diameter (min)Jacket OD (max)
HVT-51#4 to 2/00.45 (11)0.85 (22)
HVT-523/0 to 5000.70 (18)1.30 (33)
HVT-53750 to 15001.10 (28)2.15 (55)

For three-conductor 5 kV cable, order three single-conductor kits plus one MOD-3-HVT modification kit: MOD-3A-HVT for the HVT-51 and HVT-52, and MOD-3B-HVT for the HVT-53. Each MOD-3-HVT kit has 4 feet of tubing to rejacket each phase and ground conductor, sealant, plugs and a cable breakout to seal the crotch area.

HVT-Z-LC and HVT-Z-SLC Kits for LC Shield Cable

TE's catalog lists HVT-Z-LC (indoor) and HVT-Z-SLC (outdoor) kits for 1/C LC shield cable between 15 and 35 kV. They use the same ZnO stress control as the HVT-Z and can be installed upright or inverted. Kits are supplied with two pieces of #4 AWG braid for fault-current capacity, so check that the braid is compatible with your LC shield cable. Kits do not include connectors. Insulation diameter and jacket OD are in inches, with millimeters in parentheses.

Indoor / Outdoor KitConductor SizeInsulation DiameterJacket OD (max)
HVT-Z-151-LC / HVT-Z-151-SLC#4-1/00.65-0.95 (17-24)1.20 (30)
HVT-Z-152-LC / HVT-Z-152-SLC2/0-3500.85-1.25 (22-32)1.50 (38)
HVT-Z-153-LC / HVT-Z-153-SLC400-10001.10-1.75 (28-44)2.10 (53)
HVT-Z-154-LC / HVT-Z-154-SLC1250-25001.60-2.45 (41-62)2.75 (70)

HVT-ZL Longer Terminations

TE's HVT-ZL is built on the HVT-Z but is longer. TE lists it for applications that need a longer installation than the HVT-Z gives, such as coastal environments or replacing legacy HVT terminations. Each kit comes as -G indoor and -SG outdoor. Insulation diameter and jacket OD are in inches, with millimeters in parentheses. Conductor ranges are as TE prints them, and kits do not include connectors.

Indoor / Outdoor KitConductor SizeInsulation DiameterJacket OD (max)
5/8 kV (installed length 10.5 in, 267 mm)
HVT-ZL-80-G / HVT-ZL-80-SG5 kV: #4-#1 AWG; 8 kV: #6-#2 AWG0.35-0.60 (9-15)0.95 (24)
HVT-ZL-81-G / HVT-ZL-81-SG5 kV: 1/0-250 kcmil; 8 kV: #1-4/0 AWG0.60-0.95 (15-24)1.20 (30)
HVT-ZL-82-G / HVT-ZL-82-SG5 kV: 300-500 kcmil; 8 kV: 250-500 kcmil0.80-1.25 (20-32)1.50 (38)
HVT-ZL-83-G / HVT-ZL-83-SG600-1750 kcmil1.10-1.75 (28-44)2.10 (53)
HVT-ZL-84-G / HVT-ZL-84-SG5 kV: 1500-2500 kcmil; 8 kV: 2000-2500 kcmil1.60-2.45 (41-62)2.75 (70)
15 kV (installed length 15.0 in, 381 mm)
HVT-ZL-151-G / HVT-ZL-151-SG#4-1/0 AWG0.60-0.95 (15-24)1.20 (30)
HVT-ZL-152-G / HVT-ZL-152-SG2/0-350 kcmil0.80-1.25 (20-32)1.50 (38)
HVT-ZL-153-G / HVT-ZL-153-SG400-1000 kcmil1.10-1.65 (28-44)2.10 (53)
HVT-ZL-154-G / HVT-ZL-154-SG1250-2500 kcmil1.60-2.45 (41-62)2.75 (70)
25 kV (installed length 28.0 in, 711 mm)
HVT-ZL-252-G / HVT-ZL-252-SG#2-250 kcmil0.80-1.25 (20-32)1.50 (38)
HVT-ZL-253-G / HVT-ZL-253-SG300-750 kcmil1.10-1.70 (28-43)2.10 (53)
HVT-ZL-254-G / HVT-ZL-254-SG1000-2000 kcmil1.60-2.45 (41-62)2.75 (70)
35 kV (installed length 33.0 in, 838 mm)
HVT-ZL-352-G / HVT-ZL-352-SG#1-1/0 AWG0.80-1.25 (20-32)1.50 (38)
HVT-ZL-353-G / HVT-ZL-353-SG2/0-500 kcmil1.10-1.75 (28-44)2.10 (53)
HVT-ZL-354-G / HVT-ZL-354-SG750-1750 kcmil1.60-2.45 (41-62)2.75 (70)

How do I pick between HVT and HVT-Z?

  1. Voltage class. Pick 5/8, 15, 25 or 35 kV from the cable rating.
  2. Indoor or outdoor. -G for indoor, -SG for outdoor with skirts.
  3. Cable size. Measure the insulation diameter and find the kit whose range covers it, then check the conductor against the table.
  4. Space. Check the installed length for your class. TE lists 11.5 in for the 5/8 and 15 kV HVT-Z against 10.5 in and 15 in for the HVT, and 19 in for 25 and 35 kV HVT-Z against 28 in and 33 in for the HVT.
  5. Connector. If you want the lug in the kit, the HVT-Z has -T5, -T8 and -T9 ShearBolt kits.

Send us your cable and we will match the kit.

How Do You Install the Raychem HVT?

TE Connectivity's installation video for the Raychem HVT heat shrink termination. Always follow the instruction sheet packed with your kit for the exact steps and heating technique.

Heat shrink or cold shrink termination?

The HVT and HVT-Z are heat shrink, so you need a torch to install them. See our Raychem torches and accessories guide. If you would rather not use a torch, TE's cold shrink CST line covers 5 to 35 kV polymeric cable. See our Raychem CST guide.

Frequently asked questions

What voltage are the HVT and HVT-Z rated for?

Both come in 5/8, 15, 25 and 35 kV classes. Continuous current for the HVT is equal to the cable ampacity.

What does the S in SG mean?

The S marks the outdoor kit. TE's sheet says outdoor kits are tested with skirts (rain sheds), and indoor -G kits have no skirts.

Can an HVT be installed upside down?

Yes. TE says the HVT can be installed upright or inverted, and it is rated for top-feed installation.

Does the HVT work on armored cable?

Yes. TE lists standard kits for all plastic cable types, including armored cable, with one installation technique for all of them.

What standard are they qualified to?

Both are fully qualified per IEEE 48 as Class I terminations.

What makes the HVT-Z different?

It is a co-extruded one-piece termination with a zinc oxide stress-control grading layer. It can also be ordered with ShearBolt terminals.

Do they need maintenance?

TE describes the HVT material as non-tracking, maintenance free and needing no periodic cleaning.

Do they come with lugs?

Standard kits do not. The HVT-Z has -T5, -T8 and -T9 kits that include an aluminum ShearBolt terminal.

What torch do I need to install the HVT or HVT-Z?

Both are heat shrink products, so you need a propane torch with the right hose and regulator for the job. Our Raychem torches and accessories guide compares the three Raychem torch kits and the hoses and regulators that go with them.