Raychem TFT-E and TFT-R Tool Free Terminations: Sizes, Differences and How to Choose

February 28, 2024

Raychem TFT-E and TFT-R Tool Free Terminations: Sizes, Differences and How to Choose

TE Connectivity's Raychem Tool Free Terminations are cold applied elastomeric terminations for medium voltage cable. They come on a pre-lubricated, crush resistant holdout, so there is no torch and no special tooling. TE sells two separate lines with separate data sheets: the TFT-E for 15, 25 and 35 kV, and the TFT-R for 5/8, 15, 25 and 35 kV. They look alike on a price list but the part numbers and some size ranges are different, so this guide covers both.

TFT-E vs TFT-R at a Glance

From TE's TFT-E data sheet (E110), TFT-E drawing (MV_CA_TFT-E_AMS) and TFT-R data sheet (1308238). Cable ranges follow TE's July 2025 Power Transmission and Distribution catalog.

TFT-ETFT-R
Voltage classes15, 25, 35 kV. TE's drawing also lists unshedded 5/8/15 kV -G kits.5/8, 15, 25, 35 kV
CableSingle core polymeric cableSingle conductor shielded and non-shielded extruded dielectric cable
Largest conductor listed1250 kcmil1250 kcmil
HousingElastomeric housing with integral shedsElastomeric tubing, with -G indoor and -SG outdoor shielded kits
Stress controlMetal oxide matrixMetal oxide matrix
HoldoutPre-lubricated, crush resistantPre-lubricated, crush resistant
RepositioningTE says the termination can be repositioned after installationNot listed
ShearBolt kitsAluminum ShearBolt kits for 35 kVNot listed
StandardMeets or exceeds IEEE-48-1996 Class 1Not listed on the sheet
Packaging3 terminations per box3 terminations per box
Test reportsEDR-5302 (15 kV), EDR-5303 (25 kV), EDR-5299 (35 kV)The same three, plus EDR-5306 (indoor, non-shedded) and EDR-5527 (TFT-P)

TE lists these features for the line: maintenance free, long life even in highly contaminated areas, outstanding UV stability, a crush resistant core that prevents collapsing from rough handling, moisture and contamination sealing, easier installation in confined spaces, and fewer kits to cover a wide range of cable sizes (TFT-R).

TFT-E Test Ratings

TE says the TFT-E meets or exceeds IEEE-48-1996 Class 1 termination requirements, including these values. The sheet prints the DEV column as shown.

Insulation class6 h ACDEVBILDC
15 kV35 kV13 kV110 kV75 kV
25 kV55 kV21.5 kV150 kV105 kV
35 kV75 kV30 kV200 kV140 kV

TFT-E Part Number Endings: E, SG, SLC and G

The E in TFT-151E is the product line. The ending after it tells you which cable the kit is built for. This comes from TE's TFT-E drawing (MV_CA_TFT-E_AMS, 2021), which sorts every kit by cable type.

EndingExampleCable it is forGround connection
NoneTFT-152ECN and JCN cable (concentric neutral). TE's 15 kV install sheet (PII-55057) also lists flat strap neutral cable.No ground braid or clamp listed
-SGTFT-152E-SGTape shielded cable. TE's 15 kV and 25 kV SG install sheets (PII-55067 and PII-55072) also list wire shield, UniShield and lead sheath cable.Solder-blocked ground braid and solderless ground clamp
-SLCTFT-152E-SLCLongitudinally corrugated (LC) shielded cableSolder-blocked ground braid and solderless ground clamp
-GTFT-152E-GTape shielded cable, 5/8/15 kV, no shedsNot stated on the drawing

The drawing lists the -G kits only at 5/8/15 kV, in sizes 151 to 153, and only for tape shielded cable. At 15, 25 and 35 kV the E, -SG and -SLC versions come in every size shown below. TE's catalog describes LC as a longitudinally corrugated shield. If you are not sure your cable is an LC type, confirm with us before ordering.

TFT-E Sheds and Installed Length

The drawing gives the number of sheds (skirts) and the installed length L for each voltage class. TE notes that installed length can vary with the cable dimensions and the connector type.

Voltage classSizesShedsInstalled length
5/8/15 kV, -G only151 to 153010.5 in.
15 kV151 to 154311.5 in.
25 kV251 to 254515 in.
35 kV352 to 354825 in.

Sizes on the drawing are based on typical dimensions of 100% insulated cable and commonly used AEIC connectors. TE lists the nominal 100% insulation thickness as 175 mils at 15 kV, 260 mils at 25 kV and 345 mils at 35 kV. For cable made to other specifications, confirm the selection against your cable dimensions. The standard kits do not contain connectors, so order compression or solder connectors separately.

TFT-E Sizing

Sizes follow TE's July 2025 catalog. The no-ending kit for the 35 kV 352 covers a narrower range than the -SG and -SLC kits, so it gets its own row. Sizes are based on 100 and 133% concentric stranded cable dimensions. Insulation OD is in millimeters, with inches in parentheses.

VoltageKitConductor (AWG/kcmil)Insulation OD
15 kVTFT-151E / SG / SLC#2 to 25016 to 28 (0.64 to 1.09 in.)
15 kVTFT-152E / SG / SLC4/0 to 50022 to 37 (0.85 to 1.45 in.)
15 kVTFT-153E / SG / SLC500 to 75027 to 43 (1.06 to 1.70 in.)
15 kVTFT-154E / SG / SLC1000 to 125038 to 56 (1.49 to 2.20 in.)
25 kVTFT-251E / SG / SLC#1 to 2/016 to 28 (0.64 to 1.09 in.)
25 kVTFT-252E / SG / SLC#2 to 35022 to 37 (0.85 to 1.45 in.)
25 kVTFT-253E / SG / SLC250 to 75027 to 43 (1.06 to 1.70 in.)
25 kVTFT-254E / SG / SLC750 to 125038 to 56 (1.49 to 2.20 in.)
35 kVTFT-352E1/0 to 4/022 to 33 (0.85 to 1.31 in.)
35 kVTFT-352E-SG / SLC1/0 to 25022 to 37 (0.85 to 1.45 in.)
35 kVTFT-353E / SG / SLC4/0 to 35027 to 43 (1.06 to 1.70 in.)
35 kVTFT-354E / SG / SLC500 to 125038 to 56 (1.49 to 2.20 in.)

TFT-E Kits with ShearBolt Connectors

TE lists three 35 kV TFT-E kits that include an aluminum ShearBolt connector.

KitConductor (AWG/kcmil)Insulation ODConnector
TFT-353E-T51/0 to 35026 to 38 mm (1.05 to 1.48 in.)ASBT-2-350
TFT-354E-T8350 to 75035 to 46 mm (1.36 to 1.82 in.)ASBT-350-750
TFT-354E-T9600 to 100040 to 56 mm (1.57 to 2.20 in.)ASBT-600-1000

TFT-R Sizing

The TFT-R covers the 5/8 kV class and non-shielded cable, which the TFT-E sheet does not. Insulation OD is in millimeters, with inches in parentheses.

5/8 kV

TypeKitConductor (AWG/kcmil)Insulation OD
TFT-P-R, shielded, indoor, push onTFT-P-80R#6 to #210 to 16 (0.39 to 0.61 in.)
TFT-R, 5 kV, non-shielded, indoor and outdoorTFT-50R#2 to 3/013 to 20 (0.53 to 0.80 in.)
TFT-R, 5 kV, non-shielded, indoor and outdoorTFT-51R1/0 to 25016 to 28 (0.64 to 1.09 in.)
TFT-R, 5 kV, non-shielded, indoor and outdoorTFT-52R250 to 50022 to 37 (0.85 to 1.45 in.)
TFT-R, 5 kV, non-shielded, indoor and outdoorTFT-53R350 to 75027 to 43 (1.06 to 1.70 in.)

TE also lists shielded 5 and 8 kV kits, the TFT-R-G series, without sheds. They use the same part numbers as the 15 kV kits but with different conductor ranges:

Kit5 kV conductor (AWG/kcmil)8 kV conductor (AWG/kcmil)Insulation OD
TFT-150R-G#2 to 3/0#2 to 3/013 to 20 (0.53 to 0.80 in.)
TFT-151R-G2/0 to 2501/0 to 25016 to 28 (0.64 to 1.09 in.)
TFT-152R-G350 to 500250 to 50022 to 37 (0.85 to 1.45 in.)
TFT-153R-G500 to 750500 to 75027 to 43 (1.06 to 1.70 in.)

15 kV

TypeKitConductor (AWG/kcmil)Insulation OD
TFT-R-G, shielded, indoorTFT-150R-G#2 to 3/013 to 20 (0.53 to 0.80 in.)
TFT-R-G / TFT-R-SG, shielded, indoor / outdoorTFT-151R-G / TFT-151R-SG#2 to 25016 to 28 (0.64 to 1.09 in.)
TFT-R-G / TFT-R-SG, shielded, indoor / outdoorTFT-152R-G / TFT-152R-SG4/0 to 50022 to 37 (0.85 to 1.45 in.)
TFT-R-G / TFT-R-SG, shielded, indoor / outdoorTFT-153R-G / TFT-153R-SG500 to 75027 to 43 (1.06 to 1.70 in.)
TFT-R-SG, shielded, outdoorTFT-154R-SG1000 to 125038 to 56 (1.49 to 2.20 in.)

25 kV and 35 kV (outdoor)

VoltageKitConductor (AWG/kcmil)Insulation OD
25 kVTFT-251R-SG#1 to 3/016 to 28 (0.64 to 1.09 in.)
25 kVTFT-252R-SG2/0 to 50022 to 37 (0.85 to 1.45 in.)
25 kVTFT-253R-SG250 to 75027 to 43 (1.06 to 1.70 in.)
25 kVTFT-254R-SG750 to 125038 to 56 (1.49 to 2.20 in.)
35 kVTFT-352R-SG1/0 to 25022 to 37 (0.85 to 1.45 in.)
35 kVTFT-353R-SG4/0 to 50027 to 43 (1.06 to 1.70 in.)
35 kVTFT-354R-SG500 to 125038 to 56 (1.49 to 2.20 in.)

Where the TFT-E and TFT-R Sizes Differ

Compared with the TFT-R -SG kits, the TFT-E -SG and -SLC kits match at 15 kV and differ in three places at 25 and 35 kV. The no-ending TFT-E 352 kit at 35 kV covers a narrower range than either, as the sizing table above shows.

KitTFT-E (-SG / -SLC)TFT-R (-SG)
251 (25 kV)#1 to 2/0 conductor#1 to 3/0 conductor
252 (25 kV)#2 to 350 conductor2/0 to 500 conductor
353 (35 kV)4/0 to 350 conductor4/0 to 500 conductor

Accessories

ItemWhat TE lists
BRKT seriesStainless steel cable mounting brackets, in four sizes for cable diameters from 0.80 to 2.40 in.
MOD-3-TFT seriesThree conductor modification kits that rejacket the phase conductors and provide breakout seals
Lugs and pin terminalsAvailable. TE's TFT-R sheet names a complete line of Utilux copper compression terminals.

How to Pick a TFT

StepWhat to decide
1Voltage class. For 5/8 kV, the TFT-R sheet lists the full range. The TFT-E drawing also shows unshedded 5/8/15 kV -G kits for tape shielded cable.
2Shielded or non-shielded cable. Non-shielded kits are on the TFT-R sheet.
3Insulation OD. Measure the cable and pick the kit whose range covers it, then check the conductor.
4Cable type. On the TFT-E, no ending is for CN and JCN cable, -SG is for tape shielded cable (TE's 15 and 25 kV SG install sheets also list wire shield, UniShield and lead sheath cable) and -SLC is for longitudinally corrugated (LC) shielded cable. On the TFT-R, -G is indoor and -SG is outdoor, so the endings do not mean the same thing on the two lines.
5Connector. At 35 kV, the TFT-E has kits that include an aluminum ShearBolt connector. Otherwise order your lug or pin separately.

The TFT-E and TFT-R are cold applied, so they need no torch. For a cold shrink silicone alternative see the CST guide, and for heat shrink see the HVT and HVT-Z guide.

Frequently Asked Questions About the Raychem TFT

What does TFT stand for?

Tool Free Termination. TE sells the TFT-E and TFT-R as separate lines.

What is the difference between the TFT-E and TFT-R?

The TFT-E covers 15, 25 and 35 kV single core polymeric cable, with integral sheds and 35 kV ShearBolt kits. The TFT-R covers 5/8, 15, 25 and 35 kV, including non-shielded cable. Their part numbers differ, and the conductor ranges differ on the 251 and 252 kits at 25 kV and the 353 kit at 35 kV.

Do I need a torch or special tools?

No. TE describes the TFT as a cold applied system on a pre-lubricated, crush resistant holdout.

Can a TFT be repositioned after installation?

TE lists repositioning after installation as a TFT-E feature.

What cable sizes do they cover?

Up to 1250 kcmil on both lines.

How many come in a box?

Three terminations per box on both lines.

Can I use a TFT on non-shielded cable?

Yes, with the TFT-R. TE's 5 kV non-shielded kits run from TFT-50R to TFT-53R.

What do the E, SG and SLC endings mean on the TFT-E?

The E is the product line. With no ending after it, the kit is for CN and JCN cable, and TE's 15 kV sheet adds flat strap neutral. The -SG kit is for tape shielded cable. TE's 15 kV and 25 kV SG install sheets (PII-55067 and PII-55072) also list wire shield, UniShield and lead sheath cable for them. The -SLC kit is for longitudinally corrugated (LC) shielded cable. TE says both the -SG and -SLC kits contain a solder-blocked ground braid and a solderless ground clamp. The -G kits are the unshedded 5/8/15 kV versions for tape shielded cable.

What standard does the TFT meet?

TE says the TFT-E meets or exceeds IEEE-48-1996 Class 1 termination requirements. The TFT-R sheet does not state a standard.