TE Raychem Substation Bus and Lead Insulation: HVIS, HVBC, RRBB, MVCC, MVFT and BCIC-Angle

October 30, 2026

TE Raychem Substation Bus and Lead Insulation: HVIS, HVBC, RRBB, MVCC, MVFT and BCIC-Angle

Substation bus and leads come in every shape, and tubing or tape does not fit all of them. TE Raychem has a product for each case: HVIS sheet for tees and elbows, HVBC kits for cable-to-bus connections, RRBB board for interphase barriers, MVCC covers for leads and jumpers, MVFT fusion tape for retrofit wrapping and the BCIC-Angle cover for angle bus. This guide covers all six with sizes, limits and TE test reports. Specs are from TE's Raychem Wildlife & Asset Protection catalog (2019). For tubing and tape, see our BBIT and BPTM guide and HVBT guide, and for bushing covers see our BCAC and BCAC-IC guide. The TE Raychem Wildlife and Asset Protection overview compares the whole range.

Which Bus and Lead Insulation Product for Which Job

Your jobProductVoltage statement
Straight bus runsBBIT and BPTM tubingSee the BBIT and BPTM guide
Retrofit bus where equipment cannot be dismantledHVBT tapeSee the HVBT guide
Retrofit bus, self-amalgamating siliconeMVFT fusion tapeOne layer at two-thirds overlap gives flashover protection to at least 15 kV, and to 35 kV with a second layer
Bus tees, elbows and complex shapesHVIS sheet5 to 15 kV, up to 35 kV with two layers
In-line cable-to-bus connectionHVBC kitUp to 15 kV (ANSI/IEEE) and up to 36 kV (IEC)
Switchgear cabinet interphase barrierRRBB boardNo voltage rating listed
Round leads and jumpers up to 1.75 inMVCC conductor coverSuitable for up to 25 kV phase to ground
3 to 4 in angle busBCIC-Angle coverFlashover protection up to 35 kV

HVIS High Voltage Busbar Insulating Sheet

HVIS is an adhesive-coated sheet that insulates busbar and connections but does not adhere to the metal. It works alone or with other TE wildlife and asset protection products to prevent accidental bridging from birds and animals. TE lists it as UV resistant and made of anti-tracking material. Dimensions are in inches, with mm in parentheses.

Catalog numberWidthLengthPackaging
HVIS-05-(B3) NS26 (660)20 (508)Sheet
HVIS-10-(B1) NS26 (660)33 ft (10 m)Roll

Accessories hold the sheet in place during shrinking.

Catalog numberDescriptionStandard pack
HVIS-Flat (B12)36 in flat bracket for clamping HVIS on straight runs12 each
HVIS-Angle (B12)Angle brackets for clamping HVIS at 90 degree angles12 each
HVIS-Clamp (B25)Spring clamps to hold brackets on HVIS25 each

TE gives these cut sizes as a guide, based on 5/8 in bus thickness. Experiment to confirm the final cut size.

ConnectionBus width in (mm)Cut size needed in (mm)Installations per HVIS-05 sheetInstallations per HVIS-10 roll
T1 (25)11 x 9 (275 x 225)488
T2 (50)13 x 10 (325 x 250)478
T3 (75)16 x 11 (400 x 275)248
T4 (100)18 x 13 (450 x 325)244
T6 (150)22 x 17 (550 x 425)123
Elbow1 (25)11 x 7 (275 x 175)4112
Elbow2 (50)13 x 9 (325 x 225)488
Elbow3 (75)15 x 10 (375 x 250)252
Elbow4 (100)18 x 11 (450 x 275)244
Elbow6 (150)22 x 13 (550 x 325)136
Installation noteTE statement
Bus insulationBusbars are assumed to be insulated to within one inch of the joint
Cut sizeShould extend a minimum of four inches onto each leg of the joint before shrinking
SealingTo environmentally seal each leg of the bus, order S1251-50-300-1 or S1251-25-300-4 sealant strips separately
VoltageHVIS may be rated for up to 35 kV when two layers are applied
PackageHVIS-05: 3 sheets per box. HVIS-10: 1 roll per box
Test reportsEDR-5175 and EDR-5385

HVBC High Voltage Cable-to-Bus Insulation

An HVBC kit insulates and seals one phase of an in-line cable-to-busbar connection. It has heat shrinkable insulating tubing and sealant strips, plus a heat shrinkable sealing boot for multiple cable connections, and it replaces tape-and-putty methods. It is used with TE high voltage terminations, and diameter build-up over the cable is minimal. The boot allows up to four cable connectors.

Bus width 2 to 4 inBus width 5 to 6 inNumber of cablesCable size range
HVBC-41HVBC-611#4 to 1000 kcmil
HVBC-42HVBC-622#4 to 1000 kcmil
HVBC-43HVBC-633#4 to 1000 kcmil
HVBC-44HVBC-644#4 to 1000 kcmil
HVBC limit or noteTE statement
Maximum bolt length2 inches
Maximum busbar thickness5/8 inch
Maximum bare bus length9 inches
Bolt pad accessoryBP-46 fiberglass bolt pad (sleeve)
Exposed busBBIT tubing, BPTM tubing or HVBT tape can insulate the exposed busbar before the HVBC is installed
Shielded cableMust be terminated before installing the HVBC; use TE HVT terminations
Package and test report3 kits per box. EDR-5103

RRBB Interphase Insulating Barrier Board

RRBB is a non-structural interphase barrier that protects switchgear cabinets against interphase flashovers. It is made of homogeneous polymer, is UV resistant for outdoor use, and has cross-linking resistant material that can be wiped clean after power-arc events with no visible effects or surface damage, according to TE. It can be cut and drilled for mounting without special safety equipment.

Catalog numberWidth in (mm)Length in (mm)Thickness in (mm)
RRBB-6-1.25Mx1.25M-(B3)48 (1220)48 (1220)0.250 (6)
RRBB-2440/1220-6.2-BP48 (1220)96 (2440)0.250 (6)
RRBB benefitTE statement
TrackingExcellent track resistance, especially following a power arc
Dust and toolingProduces less nuisance dust and less tooling wear than other boards
DurabilityResistant to damage from solvents, mechanical impact and general wear
Test reportEDR-5311

MVCC Conductor Cover Sizes

MVCC is made from non-tracking silicone, is suited to harsh outdoor medium voltage environments, and is split for easy installation. TE says it is flexible enough for tight bends and is designed to prevent flashover from contact with birds and animals. Dimensions are in inches, with mm in parentheses.

Catalog numberConductor diameter rangeColorSupplied length (feet)
MVCC-10/.40 (B100)Up to 0.450 (11)Red2 pieces at 50 (15.24)
MVCC-G-10/.40 (B100)Up to 0.450 (11)Gray2 pieces at 50 (15.24)
MVCC-19/.75 (B50)0.50 to 0.75 (12 to 19)Red2 pieces at 25 (7.6)
MVCC-G-19/.75 (B50)0.50 to 0.75 (12 to 19)Gray2 pieces at 25 (7.6)
MVCC-25/1.0 (B25)0.75 to 1.125 (19 to 28)Red1 piece at 25 (7.6)
MVCC-G-25/1.0 (B25)0.75 to 1.125 (19 to 28)Gray1 piece at 25 (7.6)
MVCC-45/1.75 x 4 (B24)1.125 to 1.75 (28 to 44)Red6 pieces at 4 (1.2)
MVCC-G-45/1.75 x 4 (B24)1.125 to 1.75 (28 to 44)Gray6 pieces at 4 (1.2)

MVFT Medium Voltage Fusion Tape

MVFT combines silicone polymer with the versatility of a wraparound product. It sticks to itself and to other insulating materials but not to metal or porcelain, so it removes easily for maintenance. Overlapped layers amalgamate into a complete seal. It is for indoor and outdoor use.

Catalog numberColorWidth (in)Length per roll (ft)Standard pack
MVFT-G-2-12 (B4)Gray2 (50)36 (11)4 rolls

TE gives these coverage figures for the bus length one roll insulates at two-thirds overlap.

Bus shapeBus size, in (mm)Bus length per roll, ft (m)
Rectangular1.0 (25)8 (2.4)
Rectangular2.0 (50)4.7 (1.4)
Rectangular3.0 (75)3.1 (0.9)
Rectangular4.0 (100)2.3 (0.7)
Rectangular6.0 (150)1.4 (0.4)
Rectangular8.0 (200)0.4 (0.1)
Round0.5 (12)12.9 (3.9)
Round1.0 (25)7.2 (2.2)
Round2.0 (50)3.6 (1.1)
Round3.0 (75)2.2 (0.7)
Round4.0 (100)2.0 (0.6)
Square1 x 1 (25)5.7 (1.7)
Square2 x 2 (50)2.8 (0.8)
Square3 x 3 (75)1.9 (0.6)
Square4 x 4 (100)1.7 (0.5)

BCIC-Angle Bus Cover

The BCIC-Angle is a modular, wraparound cover for retrofit insulation on 3 to 4 in angle busbar when existing equipment cannot be dismantled. Overlapped sections give increased bus coverage. TE states it provides flashover protection up to 35 kV, for indoor and outdoor use.

Catalog numberColorBusbar, in (mm)Supplied length (ft)Standard pack (pieces)
BCIC-ANGLE-4X48 (B6)Red3 to 4 (75 to 100)46
BCIC-G-ANGLE-4X48 (B6)Gray3 to 4 (75 to 100)46

TE Test Reports

ProductTE test reports
HVISEDR-5175 and EDR-5385
HVBCEDR-5103
RRBBEDR-5311
MVCCEDR-5461 (Electrical Testing) and EDR-5498 (Material Test)
MVFTEDR-5465 (Qualification Report)
BCIC-AngleEDR-5594 (BCIC-ANGLE-4X48 Electrical Testing)

Frequently Asked Questions About Bus and Lead Insulation

What is HVIS for?

Insulating busbar tees, elbows and other complex shapes where tape or tubing does not fit.

What voltage is HVIS rated for?

TE lists 5 to 15 kV, and says it may be rated up to 35 kV when two layers are applied.

What do I need to seal HVIS?

Order S1251-50-300-1 or S1251-25-300-4 sealant strips separately to seal each leg of the bus.

What does one HVBC kit cover?

One phase of an in-line cable-to-bus connection. Order by bus width and number of cables.

Can HVBC go over shielded cable?

The shielded cable must be terminated first. TE says to use its HVT terminations.

Is RRBB structural?

No. TE describes it as a non-structural interphase barrier.

What voltage is MVCC rated for?

TE says MVCC is suitable for up to 25 kV phase to ground.

What conductor sizes does MVCC fit?

Four sizes fit conductor diameters up to 1.75 in: up to 0.450 in, 0.50 to 0.75 in, 0.75 to 1.125 in and 1.125 to 1.75 in.

Does MVFT stick to the bus?

No. TE says it sticks to itself and other insulating materials but not to metal or porcelain, so it can be removed for maintenance.

How much bus does one MVFT roll cover?

It depends on bus size. For example, one roll insulates 4.7 ft of 2 in rectangular bus at two-thirds overlap.

What is the BCIC-Angle for?

Retrofit insulation of 3 to 4 in angle busbar, with flashover protection up to 35 kV.

Where to Buy Bus and Lead Insulation

Powertech Associates supplies TE Raychem wildlife and asset protection products. Order online: HVIS-05-(B3) NS, HVIS-10-(B1) NS, MVCC-G-10/.40, MVCC-G-19/.75, MVCC-G-25/1.0, MVCC-G-45/1.75 x 4 or MVFT-G-2-12. For HVBC kits, RRBB board, the BCIC-Angle, red MVCC covers, accessories and sealant strips, contact Powertech Associates at info@powertech-upsc.com or (860) 678-8772.

Last updated: November 2026.

Interested in this product?

Contact us, request a quote, or order online.