Substation bus and leads come in every shape, and tubing or tape does not fit all of them. TE Raychem has a product for each case: HVIS sheet for tees and elbows, HVBC kits for cable-to-bus connections, RRBB board for interphase barriers, MVCC covers for leads and jumpers, MVFT fusion tape for retrofit wrapping and the BCIC-Angle cover for angle bus. This guide covers all six with sizes, limits and TE test reports. Specs are from TE's Raychem Wildlife & Asset Protection catalog (2019). For tubing and tape, see our BBIT and BPTM guide and HVBT guide, and for bushing covers see our BCAC and BCAC-IC guide. The TE Raychem Wildlife and Asset Protection overview compares the whole range.
| Your job | Product | Voltage statement |
|---|---|---|
| Straight bus runs | BBIT and BPTM tubing | See the BBIT and BPTM guide |
| Retrofit bus where equipment cannot be dismantled | HVBT tape | See the HVBT guide |
| Retrofit bus, self-amalgamating silicone | MVFT fusion tape | One layer at two-thirds overlap gives flashover protection to at least 15 kV, and to 35 kV with a second layer |
| Bus tees, elbows and complex shapes | HVIS sheet | 5 to 15 kV, up to 35 kV with two layers |
| In-line cable-to-bus connection | HVBC kit | Up to 15 kV (ANSI/IEEE) and up to 36 kV (IEC) |
| Switchgear cabinet interphase barrier | RRBB board | No voltage rating listed |
| Round leads and jumpers up to 1.75 in | MVCC conductor cover | Suitable for up to 25 kV phase to ground |
| 3 to 4 in angle bus | BCIC-Angle cover | Flashover protection up to 35 kV |
HVIS is an adhesive-coated sheet that insulates busbar and connections but does not adhere to the metal. It works alone or with other TE wildlife and asset protection products to prevent accidental bridging from birds and animals. TE lists it as UV resistant and made of anti-tracking material. Dimensions are in inches, with mm in parentheses.
| Catalog number | Width | Length | Packaging |
|---|---|---|---|
| HVIS-05-(B3) NS | 26 (660) | 20 (508) | Sheet |
| HVIS-10-(B1) NS | 26 (660) | 33 ft (10 m) | Roll |
Accessories hold the sheet in place during shrinking.
| Catalog number | Description | Standard pack |
|---|---|---|
| HVIS-Flat (B12) | 36 in flat bracket for clamping HVIS on straight runs | 12 each |
| HVIS-Angle (B12) | Angle brackets for clamping HVIS at 90 degree angles | 12 each |
| HVIS-Clamp (B25) | Spring clamps to hold brackets on HVIS | 25 each |
TE gives these cut sizes as a guide, based on 5/8 in bus thickness. Experiment to confirm the final cut size.
| Connection | Bus width in (mm) | Cut size needed in (mm) | Installations per HVIS-05 sheet | Installations per HVIS-10 roll |
|---|---|---|---|---|
| T | 1 (25) | 11 x 9 (275 x 225) | 4 | 88 |
| T | 2 (50) | 13 x 10 (325 x 250) | 4 | 78 |
| T | 3 (75) | 16 x 11 (400 x 275) | 2 | 48 |
| T | 4 (100) | 18 x 13 (450 x 325) | 2 | 44 |
| T | 6 (150) | 22 x 17 (550 x 425) | 1 | 23 |
| Elbow | 1 (25) | 11 x 7 (275 x 175) | 4 | 112 |
| Elbow | 2 (50) | 13 x 9 (325 x 225) | 4 | 88 |
| Elbow | 3 (75) | 15 x 10 (375 x 250) | 2 | 52 |
| Elbow | 4 (100) | 18 x 11 (450 x 275) | 2 | 44 |
| Elbow | 6 (150) | 22 x 13 (550 x 325) | 1 | 36 |
| Installation note | TE statement |
|---|---|
| Bus insulation | Busbars are assumed to be insulated to within one inch of the joint |
| Cut size | Should extend a minimum of four inches onto each leg of the joint before shrinking |
| Sealing | To environmentally seal each leg of the bus, order S1251-50-300-1 or S1251-25-300-4 sealant strips separately |
| Voltage | HVIS may be rated for up to 35 kV when two layers are applied |
| Package | HVIS-05: 3 sheets per box. HVIS-10: 1 roll per box |
| Test reports | EDR-5175 and EDR-5385 |
An HVBC kit insulates and seals one phase of an in-line cable-to-busbar connection. It has heat shrinkable insulating tubing and sealant strips, plus a heat shrinkable sealing boot for multiple cable connections, and it replaces tape-and-putty methods. It is used with TE high voltage terminations, and diameter build-up over the cable is minimal. The boot allows up to four cable connectors.
| Bus width 2 to 4 in | Bus width 5 to 6 in | Number of cables | Cable size range |
|---|---|---|---|
| HVBC-41 | HVBC-61 | 1 | #4 to 1000 kcmil |
| HVBC-42 | HVBC-62 | 2 | #4 to 1000 kcmil |
| HVBC-43 | HVBC-63 | 3 | #4 to 1000 kcmil |
| HVBC-44 | HVBC-64 | 4 | #4 to 1000 kcmil |
| HVBC limit or note | TE statement |
|---|---|
| Maximum bolt length | 2 inches |
| Maximum busbar thickness | 5/8 inch |
| Maximum bare bus length | 9 inches |
| Bolt pad accessory | BP-46 fiberglass bolt pad (sleeve) |
| Exposed bus | BBIT tubing, BPTM tubing or HVBT tape can insulate the exposed busbar before the HVBC is installed |
| Shielded cable | Must be terminated before installing the HVBC; use TE HVT terminations |
| Package and test report | 3 kits per box. EDR-5103 |
RRBB is a non-structural interphase barrier that protects switchgear cabinets against interphase flashovers. It is made of homogeneous polymer, is UV resistant for outdoor use, and has cross-linking resistant material that can be wiped clean after power-arc events with no visible effects or surface damage, according to TE. It can be cut and drilled for mounting without special safety equipment.
| Catalog number | Width in (mm) | Length in (mm) | Thickness in (mm) |
|---|---|---|---|
| RRBB-6-1.25Mx1.25M-(B3) | 48 (1220) | 48 (1220) | 0.250 (6) |
| RRBB-2440/1220-6.2-BP | 48 (1220) | 96 (2440) | 0.250 (6) |
| RRBB benefit | TE statement |
|---|---|
| Tracking | Excellent track resistance, especially following a power arc |
| Dust and tooling | Produces less nuisance dust and less tooling wear than other boards |
| Durability | Resistant to damage from solvents, mechanical impact and general wear |
| Test report | EDR-5311 |
MVCC is made from non-tracking silicone, is suited to harsh outdoor medium voltage environments, and is split for easy installation. TE says it is flexible enough for tight bends and is designed to prevent flashover from contact with birds and animals. Dimensions are in inches, with mm in parentheses.
| Catalog number | Conductor diameter range | Color | Supplied length (feet) |
|---|---|---|---|
| MVCC-10/.40 (B100) | Up to 0.450 (11) | Red | 2 pieces at 50 (15.24) |
| MVCC-G-10/.40 (B100) | Up to 0.450 (11) | Gray | 2 pieces at 50 (15.24) |
| MVCC-19/.75 (B50) | 0.50 to 0.75 (12 to 19) | Red | 2 pieces at 25 (7.6) |
| MVCC-G-19/.75 (B50) | 0.50 to 0.75 (12 to 19) | Gray | 2 pieces at 25 (7.6) |
| MVCC-25/1.0 (B25) | 0.75 to 1.125 (19 to 28) | Red | 1 piece at 25 (7.6) |
| MVCC-G-25/1.0 (B25) | 0.75 to 1.125 (19 to 28) | Gray | 1 piece at 25 (7.6) |
| MVCC-45/1.75 x 4 (B24) | 1.125 to 1.75 (28 to 44) | Red | 6 pieces at 4 (1.2) |
| MVCC-G-45/1.75 x 4 (B24) | 1.125 to 1.75 (28 to 44) | Gray | 6 pieces at 4 (1.2) |
MVFT combines silicone polymer with the versatility of a wraparound product. It sticks to itself and to other insulating materials but not to metal or porcelain, so it removes easily for maintenance. Overlapped layers amalgamate into a complete seal. It is for indoor and outdoor use.
| Catalog number | Color | Width (in) | Length per roll (ft) | Standard pack |
|---|---|---|---|---|
| MVFT-G-2-12 (B4) | Gray | 2 (50) | 36 (11) | 4 rolls |
TE gives these coverage figures for the bus length one roll insulates at two-thirds overlap.
| Bus shape | Bus size, in (mm) | Bus length per roll, ft (m) |
|---|---|---|
| Rectangular | 1.0 (25) | 8 (2.4) |
| Rectangular | 2.0 (50) | 4.7 (1.4) |
| Rectangular | 3.0 (75) | 3.1 (0.9) |
| Rectangular | 4.0 (100) | 2.3 (0.7) |
| Rectangular | 6.0 (150) | 1.4 (0.4) |
| Rectangular | 8.0 (200) | 0.4 (0.1) |
| Round | 0.5 (12) | 12.9 (3.9) |
| Round | 1.0 (25) | 7.2 (2.2) |
| Round | 2.0 (50) | 3.6 (1.1) |
| Round | 3.0 (75) | 2.2 (0.7) |
| Round | 4.0 (100) | 2.0 (0.6) |
| Square | 1 x 1 (25) | 5.7 (1.7) |
| Square | 2 x 2 (50) | 2.8 (0.8) |
| Square | 3 x 3 (75) | 1.9 (0.6) |
| Square | 4 x 4 (100) | 1.7 (0.5) |
The BCIC-Angle is a modular, wraparound cover for retrofit insulation on 3 to 4 in angle busbar when existing equipment cannot be dismantled. Overlapped sections give increased bus coverage. TE states it provides flashover protection up to 35 kV, for indoor and outdoor use.
| Catalog number | Color | Busbar, in (mm) | Supplied length (ft) | Standard pack (pieces) |
|---|---|---|---|---|
| BCIC-ANGLE-4X48 (B6) | Red | 3 to 4 (75 to 100) | 4 | 6 |
| BCIC-G-ANGLE-4X48 (B6) | Gray | 3 to 4 (75 to 100) | 4 | 6 |
| Product | TE test reports |
|---|---|
| HVIS | EDR-5175 and EDR-5385 |
| HVBC | EDR-5103 |
| RRBB | EDR-5311 |
| MVCC | EDR-5461 (Electrical Testing) and EDR-5498 (Material Test) |
| MVFT | EDR-5465 (Qualification Report) |
| BCIC-Angle | EDR-5594 (BCIC-ANGLE-4X48 Electrical Testing) |
Insulating busbar tees, elbows and other complex shapes where tape or tubing does not fit.
TE lists 5 to 15 kV, and says it may be rated up to 35 kV when two layers are applied.
Order S1251-50-300-1 or S1251-25-300-4 sealant strips separately to seal each leg of the bus.
One phase of an in-line cable-to-bus connection. Order by bus width and number of cables.
The shielded cable must be terminated first. TE says to use its HVT terminations.
No. TE describes it as a non-structural interphase barrier.
TE says MVCC is suitable for up to 25 kV phase to ground.
Four sizes fit conductor diameters up to 1.75 in: up to 0.450 in, 0.50 to 0.75 in, 0.75 to 1.125 in and 1.125 to 1.75 in.
No. TE says it sticks to itself and other insulating materials but not to metal or porcelain, so it can be removed for maintenance.
It depends on bus size. For example, one roll insulates 4.7 ft of 2 in rectangular bus at two-thirds overlap.
Retrofit insulation of 3 to 4 in angle busbar, with flashover protection up to 35 kV.
Powertech Associates supplies TE Raychem wildlife and asset protection products. Order online: HVIS-05-(B3) NS, HVIS-10-(B1) NS, MVCC-G-10/.40, MVCC-G-19/.75, MVCC-G-25/1.0, MVCC-G-45/1.75 x 4 or MVFT-G-2-12. For HVBC kits, RRBB board, the BCIC-Angle, red MVCC covers, accessories and sealant strips, contact Powertech Associates at info@powertech-upsc.com or (860) 678-8772.
Last updated: November 2026.